Stulz Driver Manual
Page 8 of 16
4.2
Client Side Node Parameters
Section Title
Nodes
Column Title Function
Legal Values
Node_Name
Provide name for node.
Up to 32 alphanumeric
characters
Node_ID
Modbus station address of physical Server node.
1-32
Protocol
Specify protocol used.
Stulz
Connection
Specify which port the device is connected to the
FieldServer.
R1-R2
1
Example
// Client Side Nodes
Nodes
Node_Name , Node_ID , Protocol , Connection
SATS1
,1
, Stulz
, R1
4.3
Client Side Map Descriptor Parameters
4.3.1 FieldServer Related Map Descriptor Parameters
Column Title
Function
Legal Values
Map_Descriptor_Name Name of this Map Descriptor.
Up to 32 alphanumeric
characters
Data_Array_Name
Name of Data Array where data is to be
stored in the FieldServer.
One of the Data Array names
from
Data_Array_Offset
Starting location in Data Array.
0 to maximum specified in
Section
Function
Function of Server Map Descriptor.
RDBC, WRBX, WRBC,
Passive_client
Scan_Interval
Buffers Update Period.
> 0.001s
4.3.2 Driver Specific Map Descriptor Parameters
Column Title
Function
Legal Values
Node_Name
Name of Node.
One of the Node names
specified in
Section
Length
Length of Map Descriptor.
When using PASSIVE_CLIENT
function, length is 1;
For Active Map Descriptors use
a length up to 232, depending
on command
Stulz_Command
Specifies the command to be read from the
device. In order to read data a legal LS
command is needed.
Specified in