PROFIBUS DP Master Driver Manual 

Page 4 of 14 

 

PROFIBUS DP MASTER DESCRIPTION  

The FieldServer PROFIBUS DP Master driver can be used to transfer I/O data with up to 125 PROFIBUS 
DP Slave devices. The FieldServer is programmed with an embedded database using the required 3

rd

 

party configuration tool. The embedded database contains information on the number of slaves and I/O 
modules to be transferred with each slave. The tool requires the input of GSD/E files for each slave to be 
connected. 

Max Nodes Supported 

FieldServer Mode 

Nodes 

Comments 

Client 

DPV1 MASTER 

(CLASS 1) ONLY 

125 

This  is  the  maximum  number  of  PROFIBUS  DP  Slaves  that  can 
be connected to the FieldServer. A maximum total of 1536 bytes 
can be transferred with all DP Slaves. 

 

 

 

DRIVER SCOPE OF SUPPLY 

2.1 

Supplied by Sierra Monitor  

Part # 

Description 

52201 

PROFIBUS Connector 

FS-8915-31  Adapter Card, PROFIBUS Master FS-B3 

 

2.2 

Provided by the Supplier of 3

r d

 Party Equipment 

2.2.1  Required 3

r d

 Party Software 

Description 

Comments 

HMS Anybus NetTool for 
PROFIBUS 

Used  to  configure  the  PROFIBUS  network  configuration  and  load  it 
directly into the PROFIBUS card. 

Vendor gsd's 

*.gsd files for all vendor devices to be on the network are required by 
HMS NetTool for completion of network configuration. 

2.2.2  Required 3

r d

 Party Configuration 

Connection to a correctly terminated PROFIBUS network. 

 

 

 

 

 

 

 

Summary of Contents for FieldServer FS-8700-122 PROFIBUS DP Master

Page 1: ...n 1 01 Document Revision 1 A FieldServer FS 8700 122 PROFIBUS DP Master Driver Manual Supplement to the FieldServer Instruction Manual APPLICABILITY EFFECTIVITY Effective for all systems manufactured...

Page 2: ...support needs related to the FieldServer product Sierra Monitor Corporation 1991 Tarob Court Milpitas CA 95035 Website www sierramonitor com U S Support Information 1 408 964 4443 1 800 727 4377 Email...

Page 3: ...4 1 FieldServer 6 4 2 Data Arrays Descriptors 6 4 3 Client Side Connection Descriptors 7 4 4 Client Side Node Descriptors 7 4 5 Client Side Map Descriptors 8 4 5 1 FieldServer Related Map Descriptor P...

Page 4: ...Y 125 This is the maximum number of PROFIBUS DP Slaves that can be connected to the FieldServer A maximum total of 1536 bytes can be transferred with all DP Slaves DRIVER SCOPE OF SUPPLY 2 1 Supplied...

Page 5: ...GND from RS 485 side 6 5V BUS2 Isolated 5V from RS 485 side 7 Not connected 8 A Line Negative RxD TxD according to RS 485 specification 9 Not connected Only A line B line and Shield are used for most...

Page 6: ...lient Side Nodes section and the data required from the Servers needs to be mapped in the Client Side Map Descriptors section Details on how to do this can be found below NOTE In the tables below indi...

Page 7: ...tions Adapters Adapter Prof_DP 4 4 Client Side Node Descriptors Section Title Nodes Column Title Function Legal Values Node_Name Provide name for Node Up to 32 alphanumeric characters Node_ID Station...

Page 8: ...ion Function of Client Map Descriptor Rdbc Wrbc 4 5 2 Driver Related Map Descriptor Parameters Column Title Function Legal Values Node_Name Name of Node from which to fetch data One of the node names...

Page 9: ..._Descriptor_Name Data_Array_Name Data_Array_Offset Function Node_Name Word_Out Word_Out 0 Wrbc PDP_SLV003 Byte_Out Byte_Out 0 Wrbc PDP_SLV003 PROFIBUS_Data_Type Address Length Scan_Interval Word 0 50...

Page 10: ...own in Section 3 Expand the PROFIBUS Master Tree select the ABM DPV device and drag it onto the Bus Configuration Screen This is the FieldServer PROFIBUS DP Master device Select Project New Expand the...

Page 11: ...ress Continue adding all other Slaves and setting their PROFIBUS addresses Right click on the ABM DPV Master device and select Object Properties Set the Master Station Address to the same as the Syste...

Page 12: ...ing other Slaves and adding modules for them as well NOTE Changing of Input and Output Addresses are not allowed All addresses must be contiguous for the PROFIBUS to work correctly Select Online Drive...

Page 13: ...iver Manual Page 13 of 14 Choose Online Download configuration to install the embedded database in the FS B35 NOTE The FS B35 must be running with a valid configuration file before it will allow downl...

Page 14: ...e Restarting FieldServer in 10 seconds Appendix A 1 2 Configuration Error Reported Ensure that the correct Map Descriptor function has been used Refer to Sections 4 5 2 and Section 4 7 Ensure that the...

Reviews: