PROFIBUS DP Master Driver Manual
Page 12 of 14
Select the first slave device, right-click on the Slot 1 line and choose Module selection. Now add I/O
modules up to the total number of bytes or words that will be transferred with this Slave as set up in the
config.csv file.
For Example, for the Map Descriptor for Slave1 using 50 Words In and Out, you would choose the
following modules:
Continue selecting other Slaves and adding modules for them as well.
NOTE: Changing of Input and Output Addresses are not allowed. All addresses must be
contiguous for the PROFIBUS to work correctly.
Select Online-> Driver selection and on the serial Tab, choose the serial port on the PC connected to the
FS-B35 by clicking on Configure-> Configure path.
Ensure that the FS-B35 FieldServer is running and that a matching configuration file with Node and Map
Descriptors for each slave configured has been downloaded to the FS-B35.
Make sure you can connect using FS-GUI to the FS-B35 and there are no configuration errors.