Z_ISE20C-TF2Z061EN
Page 1 of 3
Instruction Manual
High Precision Digital Pressure Switch
Series ZSE20C(F) / ISE20C(H)
The intended use of this digital pressure switch is to measure, monitor
and display pressure and to provide an output signal.
1 Safety Instructions
These safety instructions are intended to prevent hazardous situations
and/or equipment damage. These instructions indicate the level of
potential hazard with the labels of “Caution,” “Warning” or “Danger.”
They are all important notes for safety and must be followed in addition
to International Standards (ISO/IEC)
*1)
, and other safety regulations.
*1)
ISO 4414: Pneumatic fluid power - General rules relating to systems.
ISO 4413: Hydraulic fluid power - General rules relating to systems.
IEC 60204-1: Safety of machinery - Electrical equipment of machines.
(Part 1: General requirements)
ISO 10218-1: Robots and robotic devices - Safety requirements for
industrial robots - Part 1: Robots.
•
Refer to product catalogue, Operation Manual and Handling
Precautions for SMC Products for additional information.
•
Keep this manual in a safe place for future reference.
Caution
Caution indicates a hazard with a low level of risk which, if
not avoided, could result in minor or moderate injury.
Warning
Warning indicates a hazard with a medium level of risk
which, if not avoided, could result in death or serious injury.
Danger
Danger indicates a hazard with a high level of risk which, if
not avoided, will result in death or serious injury.
Warning
•
Always ensure compliance with relevant safety laws and
standards.
•
All work must be carried out in a safe manner by a qualified person in
compliance with applicable national regulations.
•
This product is class A equipment intended for use in an industrial
environment. There may be potential difficulties in ensuring
electromagnetic compatibility in other environments due to conducted
or radiated disturbances.
Otherwise electric shock, malfunction or product damage can result.
•
Refer to the operation manual on the SMC website (URL:
https://www.smcworld.com
) for more safety instructions.
2 Specifications
2.1 General specifications
∗
1: Value without digital filter (at 0 ms).
∗
2: If the applied pressure fluctuates around the set value, the hysteresis must be
set to a value more than the amount of fluctuation or chattering will occur.
∗
3: This setting is only available for models with the units selection function. Only
MPa or kPa is available for models without this function.
∗
4: The response time indicates when the set value is 90% in relation to the step
input.
2 Specifications (continued)
2.2 Piping / Weight specifications
Product No.
02(L) N02(L) F02(L) C01(L) A2(L) B2(L)
Port size
R1/4
NPT
1/4
G1/4 Rc1/8 URJ
1/4
TSJ
1/4
Materials in fluid contact
part
(pressure-sensing part)
Pressure sensor: SUS630, Fitting: SUS304
W
ei
gh
t
Body (rear piping)
51 g
51 g
48 g
47 g
54 g
46 g
Body (bottom piping)
77 g
78 g
74 g
65 g
81 g
72 g
Lead wire with
connector
+39 g
Leakage
1 x 10
-5
Pa
•
m
3
/s
1 x 10
-10
Pa
•
m
3
/s
2.3 Cable specifications
Conductor area
0.15 mm
2
(AWG26)
Insulator outside diameter
1.0 mm
Colour
Brown, Blue, Black, White, Grey (5 core)
Sheath outside diameter
φ
3.5
Warning
Special products (-X) might have specifications different from those
shown in this section. Contact SMC for specific drawings.
3 Name and function of product parts
Operation light: Displays the switch operating condition.
LCD display: Displays the current status of pressure, setting mode,
selected display units and error code.
4 types of display can be selected for the main display:
Single colour of constant red or green; or switching from
red to green or green to red corresponding to the output.
The indication for the sub display is orange.
Main display:
Displays pressure measurement values and error
codes. (2-colour display)
Sub display (left): Displays items. (Orange)
Sub display (right): Displays set values, peak and bottom values.
(Orange)
UP button: Increases mode and ON/OFF set values.
DOWN button: Decreases mode and ON/OFF set values.
SET button: Press this button to change mode and to confirm
settings.
Unit display: Indicates the units currently selected (only for kPa and
MPa).
4 Installation
4.1 Installation
Warning
Do not install the product unless the safety instructions have been read
and understood.
4.1.1 Mounting
•
Mount the optional bracket and panel mount adapter to the pressure
switch.
•
When the pressure switch is to be mounted in a place where water
and dust splashes occur, insert a tube into the atmospheric vent port
of the pressure switch (refer to “Tube attachment”).
4.1.2 Mounting with bracket
•
Mount the bracket to the body with mounting screws (Self tapping
screws: Nominal size 3 x 8L (2 pcs)), then set the body to the
specified position.
∗
: Tighten the bracket mounting screws to a torque of 0.5 ±0.05 N•m.
Self-tapping screws are used and should not be re-used several times.
•
Rear Piping
•
Bracket A (Part No.: ZS-46-A1)
•
Bottom Piping
•
Bracket C (Part No.: ZS-46-E)
4.1.3 Mounting with panel mount adapter
•
Rear Piping
•
Mount part (a) to the front of the body and fix it. Then insert the body
with (a) into the panel until (a) comes into contact with the panel front
surface. Next, mount part (b) to the body from the rear and insert it
until (b) comes into contact with the panel.
•
Panel mount adapter (Part No.: ZS-46-B)
Panel mount a Front protective cover (Part No.: ZS-46-D)
∗
: The panel mount adapter can be rotated through 90 degrees for mounting.
ORIGINAL INSTRUCTIONS
Product No.
ZSE20C
(Vacuum
pressure)
ZSE20CF
(Compound
pressure)
ISE20C
(Positive
pressure)
ISE20CH
(Positive
pressure)
Applicable fluid
Fluids which do not corrode SUS630, SUS304
Pre
ss
ure
Rated pressure range
0.0 to
-101.0 kPa
-100.0 to
100.0 kPa
-0.100 to
1.000
MPa
-0.100 to
2.000
MPa
Display/Set pressure
range
10.0 to
-105.0 kPa
-105.0 to
105.0 kPa
-0.105 to
1.050
MPa
-0.105 to
2.100
MPa
Display/Min. setting
unit
0.1 kPa
0.001 MPa
Proof pressure
500 kPa
2 MPa
4 MPa
Pow
er
s
uppl
y Power supply voltage
12 to 24 VDC (±10%), ripple max. 10% (p-p)
Current consumption
35 mA or less
Protection
Polarity protection
Accu
ra
cy
Display accuracy
±
2%F.S.
±
1 digit
(at ambient temperature 25
±
3
o
C)
Repeatability
±
0.2%F.S.
±
1 digit
Analogue output
accuracy
±
2.5%F.S. (at ambient temperature 25
±
3
o
C)
Analogue output
linearity
±
1%F.S.
Temperature
characteristics
±
3%F.S. (25
o
C standard)
Sw
itc
h o
ut
put
Output type
Select from NPN or PNP open collector output
Output mode
Hysteresis mode, window comparator mode,
error output, switch output off
Switch operation
Normal output, reversed output
Maximum load
current
80 mA
Maximum applied
voltage
30 V (during NPN output)
Internal voltage drop
(Residual voltage)
1.5 V or less (Load current 80 mA)
Delay time
∗
1
1.5 ms or less, Variable at 0 to 60 s/0.01 s step
H
yst
er
esi
s
Hysteresis
mode
Variable from 0
∗
2
Window
comparator
mode
Short circuit
protection
Provided
Dis
pla
y
Unit
∗
3
MPa, kPa, kgf/cm
2
,
bar, psi, InHg, mmHg
MPa, kPa, kgf/cm
2
,
bar, psi
Display type
LCD
Number of displays
3-screen display (Main display, sub display x 2)
Display colour
1) Main display: Red/Green
2) Sub display: Orange
Number of display
digits
Main display: 4 digits (7-segments)
Sub display: 4 digits (Upper 1 digit 11-segments,
7-segments for other)
Operation light
LED is ON when switch output is ON
(OUT1, OUT2: Orange)
Digital filter
∗
4
Variable at 0 to 30 s/0.01 s step
Env
iro
nm
ent
Enclosure
IP65
Withstand voltage
250 VAC for 1 minute between terminals and
housing
Insulation resistance
2 MΩ or
more between terminals and housing
(with 50 VDC megger)
Ambient temperature
range
Operation: -5 to 50
o
C, Storage: -10 to 60
o
C
(No condensation or freezing)
Operating humidity
range
Operation, Storage: 35 to 85%RH (No
condensation)
Length of lead wire with
connector
2 m