background image

 

VXSS-TFR48 

 

Installation and Maintenance Manual 

VXS Zero Pressure Differential Type 
Pilot operated 2 port solenoid valve 

For Steam and Heated water

 

 

1 Safety Instructions 

This manual contains essential information for the protection of users and 
others from possible injury and/or equipment damage. 

  Read this manual before using the product, to ensure correct handling, 

and read the manuals of related apparatus before use. 

  Keep this manual in a safe place for future reference. 

  These  instructions  indicate  the  level  of  potential  hazard  by  label  of 

“Caution”,  “Warning”  or  “Danger”,  followed  by  important  safety 
information which must be carefully followed. 

  To  ensure  safety  of  personnel  and  equipment  the  safety  instructions  in 

this  manual  and  the  product  catalogue  must  be  observed,  along  with 
other relevant safety practices. 

 

 

 Caution 

Indicates a hazard with a low level of risk, which if not 
avoided, could result in minor or moderate injury. 

 

 Warning 

Indicates a hazard with a medium level of risk, which 
if not avoided, could result in death or serious injury. 

 

 Danger 

Indicates a hazard with a high level of risk, which if 
not avoided, will result in death or serious injury. 

 

Warning 

 

The  compatibility  of  equipment  is  the  responsibility  of  the  person 
who designs the system or decides its specifications. 

Since  the  products  specified  here  can  be  used  in  various  operating 

conditions,  their  compatibility  with  a  specific  system  must  be  based  on 
specifications  or  after  analysis  and/or  tests  to  meet  specific 
requirements. 

 

Only  trained  personnel  should  operate  pneumatically  operated 
machinery and equipment. 

The fluid can be dangerous if an operator is unfamiliar with it. Assembly, 
handling  or  repair  of  the  system  should  be  performed  by  trained  and 
experienced personnel. 

 

Do  not  service  machinery/equipment  or  attempt  to  remove 
components until safety is confirmed. 

1)  Inspection  and  maintenance  of  machinery/equipment  should  only  be 
performed  after  confirmation  of  safe  locked-out  control  positions. 
Measures to prevent danger from the fluid should also be taken. 
2)  When  equipment  is  to  be  removed,  confirm  the  safety  processes  as 
mentioned above. Release the fluid pressure and be certain there is no 
danger  from  fluid  leakage  or  fluid  remaining  in  the  system.  Switch  off 
electrical supplies. 
3) Before machinery/equipment is re-started, ensure all safety measures 
are being implemented. 

 

Do not use this product outside of the specifications. Contact SMC 
if it is to be used in any of the following conditions: 

1) Conditions and environments beyond the given specifications, or if the 
product is to be used outdoors. 
2) Installations in conjunction with atomic energy, railway, air navigation, 
vehicles, medical equipment, food and beverage, recreation equipment, 
emergency stop circuits, press applications, or safety equipment. 
3) An application which has the possibility of having negative effects on 
people, property, or animals, requiring special safety analysis.  

 

Caution 

  Ensure that the air supply system is filtered to 5  m. 

 
 

2 Specifications 

2.1  General Specifications 

Va

lve

 

speci

ficat

ions

 

Valve construction 

Zero differential pressure pilot operated 2 

port piston type 

Withstand pressure (with 
water) 

2.0 MPa 

Maximum system pressure 

1.0 MPa 

Maximum operating  
pressure differential 

1.0 MPa

 

Minimum operating  
pressure differential 

0 MPa

Note 1)

 

Body material 

Brass (C37),  Stainless steel 

Seal material 

(Note 3)

 

FKM 

Enclosure 

Dust-tight, Water jet-proof type (IP65) 

Environment 

Location without corrosive or explosive 

gases 

Co

il 

speci

ficat

ions

 

 

Rated voltage 

AC 

100 VAC, 200VAC, 110VAC, 230VAC, 

(220VAC, 240VAC, 48VAC, 24VAC)

Note 2)

 

DC 

24 VDC 

Allowable voltage fluctuation 

±10% of rated voltage 

Allowable leakage 
voltage 

AC  

5% or less of rated voltage 

DC 

2% or less of rated voltage 

Coil insulation type 

Class H 

Note 1) The operation of the valve may be unstable due to the capacity of the 
pressure supply source such as pumps and compressors or the pressure loss by the 
orifice of piping. Please contact SMC to check if the required valve size can be used 
in the application. Contact SMC for the compatibility of the circuit and valve size. 
Note 2) Voltage in brackets ( ) indicates special voltage.

 

 

2.2  Coil Specifications 
2.2.1 Normally Closed (N.C.) 
DC Specification

 

Model 

Power consumption (W)

Note1)

 

Temperature rise (°C)

Note2)

 

VXS23/24

 

12 

100 

VXS25/26

 

15 

100 

Note 1: Power consumption: The value at ambient temperature of 20°C and when the 
rated voltage is applied. (Variation: ±10%). 

Note  2:  The  value  at  ambient  temperature  of  20°C  and  when  the  rated  voltage  is 
applied. The value depends on the ambient environment. This is for reference. 

2.2.2 Normally Closed (N.C.) 
AC Specification (Built-in Full-wave Rectifier Type)

 

Model 

Apparent power (VA)

Note 1, 2)

 

Temperature rise (°C)

Note 3)

 

VXS23/24

 

12 

100 

VXS25/26

 

15 

100 

Note  1:  Power  consumption,  apparent  power:  The  value  at  ambient  temperature  of 
20°C and when the rated voltage is applied. (Variation: ±10%) 
Note 2: There is no difference in the frequency and the inrush and energized apparent 
power, since a rectifying circuit is used for AC. (Built-in full-wave rectifier type). 
Note  3:  The  value  at  ambient  temperature  of  20°C  and  when  the  rated  voltage  is 
applied. The value depends on the ambient environment. This is for reference.

 

 
2.3  Model/Valve specifications 
For STEAM / Single Unit (Can be used with heated water) 
Normally closed (N.C.) 
C37, Stainless steel body 

Size 

Port 
Size 

Orifice 

Dia. 

(mm) 

Model 

Flow characteristics 

Weight

Note)

 

(g) 

 

 

Av 

(x 10

-6

 m

2

Cv 

1/4 

10 

VXS235 

58 

2.4 

600 

3/8 

67 

2.8 

1/2 

15 

VXS245 

130 

5.3 

720 

3/4 

20 

VXS255 

220 

9.2 

1100 

25 

VXS265 

290 

12.0 

1300 

Note) Weight of Grommet type. Add 10g for Conduit type, 30g for DIN terminal,

 

60g 

for Conduit terminal type. 
 

Ambient and fluid temperature 

Fluid 

Temperature (°C) 

Ambient temperature (°C) 

Steam 

183 or less 

-20 to 60 

Heated water 

99 or less 

Note) With no freezing. 
 

2 Specifications (continued) 

Valve Internal Leakage Rate 

Fluid 

Seal Material 

Leakage rate

Note) 

Steam 

FKM

 

1 cm

3

/min or less 

Heated water 

0.1 cm

3

/min or less 

Valve External Leakage Rate 

Fluid 

Seal Material 

Leakage rate

Note) 

Steam 

FKM

 

1 cm

3

/min or less 

Heated water 

0.1 cm

3

/min or less 

Note) Leakage is the value at ambient temperature 20°C. 
 

 

2.4  Pneumatic Symbol 
2.4.1 Valve 

Valve

 

Symbol

 

Normally closed (N.C.)

 

 

Table 1 

 
 
 
 
 
 
 
 
 
 
 
 
 
 

3 Installation 

Warning 

  Do not install the product unless the safety instructions have been read 

and understood. 

 

3.1  VXS Valve Mounting Bracket  
C37, Stainless steel (Bracket optional) 

 

 

Figure 1 

 

Model 

Port 
size 

(mm) 

Bracket Mounting 

(mm) 

VXS23 

1/4, 3/8 

10.5 

56 

75 

30 

31 

37 

35 

10 

VXS24 

1/2 

14 

56 

75 

34 

35 

41 

35 

14 

VXS25 

3/4 

17 

70.5 

92 

39 

43 

46 

33 

15.2 

VXS26 

20 

70.5 

92 

41 

45 

48 

37 

17.2 

Table 2 

 
 
 

3 Installation (continued) 

3.2  Environment 

Warning 

  Do  not  use  in  an  environment  where  corrosive  gases,  chemicals,  salt 

water, water, water vapour are present or where there is direct contact 
with any of these. 

  Do not use in an explosive atmosphere. 

  Do not expose to direct sunlight. Use a suitable protective cover. 

  Do  not  install  in  a  location  subject  to  vibration  or  impact.  Check  the 

product specifications. 

  Do not mount in a location exposed to radiant heat. 

  Employ suitable protective measures in locations where there is contact 

with water droplets, oil or welding splatter, etc. 

 

3.3  Piping 

Caution 

  Before  connecting  piping,  it  should  be  thoroughly  blown  out  with  air 

(flushed)  or  washed  to  remove  chips,  cutting  oil  and  other  debris  from 
inside the pipe. 

  Avoid  connecting  ground  lines  to  piping,  as  this  may  cause  electrolytic 

corrosion of the system. 

  When installing piping or fittings, ensure sealant material does not enter 

inside the port. When using seal tape, leave 1.5 to 2 threads exposed on 
the end of the pipe/fitting.  

  Tighten fittings to the specified tightening torque, see Table 3. 

  Install piping so that it does not apply pulling, pressing, bending or other 

forces on the valve body. 

  When connecting piping, avoid mistakes regarding the supply port. 

  Steam  generated  by  a  boiler  contains  a  large  amount  of  drainage; 

ensure to operate with a drain trap installed. 

  Avoid  installing  piping  to  the  valve  at  the  lowest  point  of  the  layout.  If 

condensate  accumulates  in  the  valve  or  adjacent  piping,  this  could 
cause  steam  hammer.  If  steam  hammer  causes  a  problem,  install  a 
bypass to discharge condensate from the piping. 

  If the effective area of the piping on the fluid supply side is restricted, the 

operating  time  may  become  unstable  due  to  the  differential  pressure 
fluctuation when the valve is closed.

 

 

Thread 

Tightening Torque N•m 

Rc 1/4 

12 to 14 

Rc 3/8 

22 to 24 

Rc 1/2 

28 to 30 

Rc 3/4 

28 to 30 

Rc 1 

36 to 38 

Table 3 

3 Installation (continued) 

3.3.1 Valve Ports 
C37, Stainless steel 
 

 

Figure 2 

 
 
 
 

 