Trouble shooting 

Problem

 

When the valve is failing, use this flow chart 
to  clarify  the  cause  of  the  failure  and  take 
countermeasures appropriate for the cause.

 

Possible cause

 

Countermeasures

 

Operation 

failure 

 

Air is not 

switched. 

 

1) Operation failure or sticking of the main 

valve. 

Foreign matter from the piping and air source 

got  caught  in  the  main  valve  of  the  valve, 
causing a malfunction. 

Malfunction occurred due to sticking such as 

swelling of the rubber part of the main valve. 

- Replace the valve. 
- Clean the air supply. 
- If incorrect oil has been used for lubrication, 

remove the oil by air blow. 

-  If  there  is  a  large  amount  of  condensate, 

install an auto drain or a dryer. 

 

2) Reduced pressure 

Air source pressure is reduced and minimum 
operating pressure of the valve was not reached, 
causing an operation failure. 

 

- Adjust the pressure within the specification 

range for the valve. 

3) Excessive oil supply 

Due to excessive lubrication, oil accumulated 
inside the valve, causing malfunction. 

 

-  Reduce  the  amount  of  lubrication  to  the 

amount  at  which  the  oil  does  not  splash 
from the exhaust port [ 3(R), vent port]. 

1) Non-conforming of electric system 

Incorrect wiring 

- Fuse blown out, lead wire broken 
-  Incorrect  contact  at  the  contact  and 

connection 

- Sequencer non-conforming 
- Supply voltage insufficient 

 

 

 

- Check all parts and replace the part,   

if necessary. 

 

- Check the supply voltage. 

2) Drop of supply voltage 

Operation failure of the valve due to voltage 
drop. 

- Check the supply voltage. Take corrective 

action if voltage drop is confirmed. 

3)  Non-conforming  of  the  installed  pilot 
valve 

- Broken wire in the coil or burnout 
(High supply voltage, incorrect coil specification, 
entry of water) 

- Replace the valve. 

1) Leakage current 

Operation failure of the valve occurred due 
to residual voltage. 

(Valve is not turned OFF) 

Check the residual voltage. 
Keep the residual voltage at 3% or less of 
the rated voltage (DC coil).   

2) Non-conformance of the installed pilot 
valve 

- Foreign matter is caught in the moving part 

of the valve (or pilot valve). 

-  Swelling  of  rubber  parts  inside  the  valve   

(or pilot valve) 

- Clean the air supply. 
- Eliminate foreign matter with air blow. 
- Replace the valve when actions above do 

not improve the condition. 

The valve operate when 
the manual override but-
ton is pushed? 

No 

 

Energized?   
Is valve switched? 

No 

 

YES 

YES 

Summary of Contents for VP500 Series

Page 1: ...Doc No VP500 OMZ0005 PRODUCT NAME 3 Port Solenoid Valve Modular Type Residual Pressure Release Valve MODEL Series VP 46E Series 5 7...

Page 2: ...Contents Contents 1 Safety Instructions 2 3 Design Selection 4 5 Mounting 5 Piping 5 Wiring 5 Lubrication 5 Air Supply 5 6 Operating Environment 6 Maintenance 6 Specific Product Precautions 7 8 Troubl...

Page 3: ...equipment failure when configuring the equipment 2 Only personnel with appropriate training should operate machinery and equipment The product specified here may become unsafe if handled incorrectly T...

Page 4: ...of the product 3 Prior to using SMC products please read and understand the warranty terms and disclaimers noted in the specified catalog for the particular products 2 Vacuum pads are excluded from th...

Page 5: ...hat the leakage voltage will increase when a resistor is used in parallel with a switching element or when a C R circuit surge voltage suppressor is used for protecting a switching device because of t...

Page 6: ...ied voltage When electric power is connected to valve be careful to apply the proper voltage Improper voltage may cause malfunction or coil damage 3 Check the connections Check if the connections are...

Page 7: ...tact with oil weld spatter etc exercise preventive measures 9 When the valve is mounted in a control panel make sure the ambient temperature is within the specifications of the valve 1 Temperature of...

Page 8: ...side of the range of supported sizes 3 5 to 7 will not satisfy IP65 enclosure standards Also be sure to tighten the gland nut and holding screw within their specified torque ranges After separating th...

Page 9: ...angerous situation due to air accumulated between the check valve and the pilot valve Soft start up function When the soft start up function is selected the initial pressure of the pneumatic system ca...

Page 10: ...e oil does not splash from the exhaust port 3 R vent port 1 Non conforming of electric system Incorrect wiring Fuse blown out lead wire broken Incorrect contact at the contact and connection Sequencer...

Page 11: ...reased because foreign matter get caught in the main valve Replace the valve Clean the air supply 2 Sealing failure of the actuator cylinder Refer to the operation manual of the actuator for details 1...

Page 12: ...Chiyoda ku Tokyo 101 0021 JAPAN Tel 81 3 5207 8249 Fax 81 3 5298 5362 URL https www smcworld com Note Specifications are subject to change without prior notice and any obligation on the part of the m...

Reviews: