3.3 Electrical connection

CAUTION

When DC power is connected to a solenoid valve equipped with light and/or surge voltage suppressor, check
for polarity indications.

For polarity indications:

No diode to protect polarity: if polarity connection is wrong, the diode in the valve or switching device at
control equipment or power supply may be damaged.
With diode to protect polarity: if polarity connection is wrong, the valve does not switch.

CAUTION: Light/surge 

CAUTION: Connection of 24V 

voltage suppressor

or more DC

For the grommet type, connect the positive (+) side to the red
lead wire and connect the negative (-) side to the black lead wire.
For the DIN terminal, connect the positive (+) side to the
connector’s No.1 terminal and connect the negative (-) side to the
No.2 terminal. 
(See the markings on the terminal block.)

For 12V or less DC, positive (+) and negative (-) can be
connected in either direction.

CAUTION: Use of DIN Connector 

Connection procedure

Loosen the holding screw, and pull the connector out of the solenoid valve terminal block.
After removing the holding screw, insert the flat head screw driver, etc. into the notch on the bottom of
the terminal block and pry it up, separating the
terminal block and the housing.
Loosen the terminal screws (slotted screws) on 
the terminal block, insert the core of the lead 
wire into the terminal in accordance with the
prescribed connection method, and attach 
securely with the terminal screws.
Fasten the cord by screwing in the gland nut.

Cord entry changing procedure

After separating the terminal block and housing, 

the cord entry direction can be changed by 

attaching the housing in the desired direction 

(4 directions in 90° increments).

*When equipped with light, handle with care so 

that the light is not damaged by the cord’s lead 

wires, etc.

Precautions

The connector should be inserted and pulled out in a straight line without tilting diagonally.

Compatible cables

Cord outside diameter: ø4 to ø6.5 (Reference)

0.5mm

2

equivalent to JISC3306, 2 wire or 3 wire

Connector part no.: VK300-37-1

Part No. for connector with light

Circuit diagram for connector with light

Rated voltage

Rating symbol

Part No.

100VAC

A1

VK300-37-2-01

200VAC

A2

VK300-37-2-02

240VAC

A3

VK300-37-2-07

6VDC

LW06

VK300-37-4-51

12VDC

LW2

VK300-37-4-06

24VDC

LD4

VK300-37-3-05

48VDC

LD8

VK300-37-3-53

3.4 Mounting

CAUTION

After confirming the installation of the
gaskets, securely tighten the screws to the
tightening torque shown in the table below:

The bushing may be damaged if the tightening 
torque of 0.8Nm is exceeded. In the event that
damage does occur,  be sure to replace the
bushing.

2 sets per unit are required.

3.5 Lubrication

CAUTION

SMC products have been lubricated for life at manufacturer, and do not require lubrication in
service.

If a lubricant is used in the system, use turbine oil Class 1(no additive), ISO VG32. Once lubricant
is used in the system, lubrication must be continued because the original lubricant applied during
manufacturing will be washed away.

4

SETTINGS AND PROGRAMMING 

4.1 Manual override operation

WARNING

When the manual override is operated, connected equipment will be actuated. 
Confirm safety before operating.

Non-locking push type (tool required)

There are manual overrides in 2 directions, on 
the top and on the side (solenoid side). 
By pressing either of the manual overrides in 
the direction of the arrow (

) until it stops

(approx. 1mm), it will turn ON, and it turns 
OFF when released.

5

MAINTENANCE

WARNING

Not following proper procedures could cause the product to malfunction and could lead to damage
to the equipment or machine.

If handled improperly, compressed air can be dangerous. Assembly, handling and repair of
pneumatic system should be performed by qualified personnel only.

Drain: remove condensate from the filter bowl on a regular basis.

Shut-down before maintenance: before attempting any kind of maintenance make sure the supply
pressure is shut off and all residual air pressure is released from the system to be worked on.

Start-up after maintenance: apply operating pressure and power to the equipment and check for
proper operation and possible air leaks. If operation is abnormal, please verify product set-up
parameters.

Do not make any modification to the product

Do not disassemble the product, unless required by installation or maintenance instructions.

5.1 Manifold mounting

Refer to paragraph 3.4, for mounting valves onto manifolds.

6

LIMITATIONS OF USE

WARNING

Do not exceed any of the specifications laid out in section 2 of this document or the specific product
catalogue.

Long continuous loading time

When power will be applied continuously for extended periods of time, use type VKF33*E. However, it cannot
be used with high frequency. Contact SMC if it will be operated more than once a day.

Be sure to perform switching at least once every 30 days.

CAUTION

Leakage voltage

Particulary when using a resistor in parallel with a switching
element, take note that leakage voltage will increase due to
leakage current flowing through the resistor. Limit the 
amount of residual leakage voltage to the following values.

For AC coil: 20% or less of rated voltage
For DC coil: 2% or less of rated voltage

Low temperature operation

Operation is possible to -10°C, but measures should be taken to avoid solidification or freezing of drainage
and moisture, etc.

Mounting orientation

The mounting orientation is unrestricted.

7

EUROPEAN CONTACT LIST

SMC Corporation

Country

Telephone

Country

Telephone

Austria

(43) 2262-62 280

Italy

(39) 02-92711 

Belgium

(32) 3-355 1464 

Netherlands

(31) 20-531 8888 

Czech Republic

(420) 5-414 24611 

Norway

(47) 67 12 90 20 

Denmark

(45) 70 25 29 00 

Poland

(48) 22-548 50 85 

Finland

(358) 9-859 580 

Portugal

(351) 22 610 89 22

France

(33) 1-64 76 1000 

Spain

(34) 945-18 4100 

Germany

(49) 6103 4020 

Sweden

(46) 8-603 0700 

Greece

(30) 1- 342 6076 

Switzerland

(41) 52-396 3131 

Hungary

(36) 1-371 1343 

Turkey

(90) 212 221 1512 

Ireland

(351) 1-403 9000 

United Kingdom

(44) 1908-56 3888 

Websites

SMC Corporation

www.smcworld.com

SMC Europe

www.smceu.com

Bushing assembly part no.

VKF300-6A-1

Grommet type

DIN terminal

Red (+)

Black (-)

Surge voltage

suppressor

* Marking

Light
(built into connector

Surge voltage

suppressor

(built into 
terminal block)

* Markings

For 24V or more DC

For AC and 12V or less DC

1

(-)

(+)

2

Gland nut

Washer

Grommet
(rubber)

Holding screw

Light mounting location

Terminal block

Notch

Terminal screw

(3 places)

Rating symbol

(see table below)

Housing

Appropriate tightening torque (Nm)

0.6 to 0.8

AC

Circuit diagram

12VDC or less

Circuit diagram

24VDC or more
Circuit diagram

LED

NL

R

LED

R

R

2

2

2

1

1

1

NL: Neon light

R: Resistor

LED: Light emitting diode

R: Resistor

D: Protective diode

LED: Light emitting diode

R: Resistor

Mounting screw

Bushing

Switching element

Valve

OFF

Leakage current

Power
supply

Resistor

Leakage

voltage

Hole dia. ø5

ø9

D

VKF300-TFH35GB 