Communication Format
INR-244-831
3-7
3.7
Communication Example
Communication example of request message to read
Request message from master: Request the product having a set address of 1 to read the measured
temperature at that moment.
Response message from the product: Send the measured temperature (00250 =25.0
o
C) at that moment.
Request message to read (from master)
Code
Symbol/Data
ASCII code
①
Start code
STX
02H
②
Address
01
30H
31H
③
Required content
R (read)
52H
④
Identifier
PV1
50H
56H
31H
⑤
Numeric data
00250
30H
30H
32H
35H
30H
⑥
End code
ETX
03H
⑦
BCC data: Request
65H
Response
06H
⑧
Acknowledge code
ACK
06H
Response message from the product
02 30 31 52 50 56 31 03 65
①
③
④
⑥ ⑦