Details of Communication Format
HEC
4-4
<Specifying unit>
Host
→
SOH
UT
ENQ
34H
Check sum
CR
(
H
)
(
L
)
←
Thermo-con
SOH
UT STX 34H
Data
ETX
Check sum
CR
D1
D2
D3
(
H
)
(
L
)
Host
→
ACK
UT CR
(Possible to omit)
Data (D2, D2, D3) changes following bit line to ASCII code. (1 is for ON, 0 is for OFF)
D1
2
3
2
2
2
1
2
0
High temp. cut off alarm
ERR12
Low temp. cut off alarm
ERR13
Unused
Output failure alarm
ERR15
D2
2
3
2
2
2
1
2
0
Upper temperature limit alarm WRN
Lower temperature limit alarm WRN
Thermostat alarm ERR14
DC power supply failure alarm
ERR11
D3
2
3
2
2
2
1
2
0
External sensor failure alarm ERR18
Internal sensor failure alarm ERR17
During Auto tuning or auto tuning warning ERR19
Flow switch alarm ERR16 or level switch alarm ERR20
When some alarms/warnings go off at the same time, D1 to D3 reaches the added value.
Ex.
When the “Upper temperature limit alarm” and the “DC power voltage alarm” go off simultaneously,
D2 will be 2
3
X1+2
2
X0+2
1
X0+2
0
X1=9(=39H).