-31-
No.PF
※※
-OMY0002
■
Default settings
Item (Main display)
Default settings (Sub display)
Page
[F 0]
[rEF ] Reference condition
[ Std] Standard condition
Page
[Unit] Unit selection function
1
[ L] L/min
[NorP] SW output PNP/NPN setting
[ PnP] PNP output
[i_o ] SW/external input setting
2
[ oUt] SW output
[F 1]
[oUt1] Output mode of OUT1
[ HYS] Hysteresis mode
Page
[1ot ] Switch operation of OUT1
[ 1_P] Normal output
[P_1 ] Set value of OUT1
50% of maximums rated flow range
[ 250] 250 L/min (500 L type)
[ 500] 500 L/min (1000 L type)
[1000] 1000 L/min (2000 L type)
[H_1 ] Hysteresis of OUT1
5% of maximums rated flow range
[ 25] 25 L/min (500 L type)
[ 50] 50 L/min (1000 L type)
[ 100] 100 L/min (2000 L type)
[dtH1] ON delay time
[0.00] 0.00 s
[dtL1] OFF delay time
[0.00] 0.00 s
[ CoL] Display colour of OUT1
[1SoG] Green when ON, Red when OFF (OUT1)
[F 2]
3
[oUt2] Output mode of OUT2
[ HYS] Hysteresis mode
Page
[2ot ] Switch operation of OUT2
[ 2_P] Normal output
[P_2 ] Set value of OUT2
50% of maximums rated flow range
[ 250] 250 L/min (500 L type)
[ 500] 500 L/min (1000 L type)
[1000] 1000 L/min (2000 L type)
[H_2 ] Hysteresis of OUT2
5% of maximums rated flow range
[ 25] 25 L/min (500 L type)
[ 50] 50 L/min (1000 L type)
[ 100] 100 L/min (2000 L type)
[dtH2] ON delay time
[0.00] 0.00 s
[dtL2] OFF delay time
[0.00] 0.00 s
[CoL ] Display colour of OUT2
[1SoG] Green when ON, Red when OFF (OUT1)
[F 3]
[FiL ] Digital filter setting
[ 1.0] 1.0 s
Page
[F10]
[Sub ] Sub display
[ dEF] Standard (Set value of OUT1)
Page
[F14]
[Cut ] Zero cut-off setting
[ 1.0] 1.0%
Page
[F20]
[inP ] External input setting
2
[ rAC] Accumulated value reset
Page
[F22]
[AoUt] Analogue output setting
4
[ 1-5] 1 to 5 V (Analogue voltage type)
[4-20] 4 to 20 mA (Analogue current type)
Page
[F30]
[SAvE] Accumulated value hold setting [ oFF] Not held
Page
[F80]
[diSP] Display OFF mode
[ oN] Normal display (Display ON)
Page
[F81]
[P in ] Security code
[ oFF] Not used
Page
[F90]
[ ALL] Setting of all functions
[ oFF] Not used
Page
[F96]
[S_in] Check of input signal
No setting due to input signal setting
Page
[F98]
[tESt] OUT Output check
[ n] Normal output
Page
[F99]
[ini ] Reset to the default settings
[ oFF] Reset OFF
Page
1: This setting is only available for models with the unit selection function.
2: This setting is only available for models with the external input.
3:
Only available for models with switch outputs for OUT2.