-78-
No.PF
※※
-OMX0002
●
Product individual parameters
Index
Sub
index
Access
1
Parameter
Data
type
2
Initial
value
Data
storage
3
Set value
4
Remarks
dec
hex
1000 0x03E8
0
R/W
Unit
(Selection of display unit)
U8
0
Y
0: L/min (L)
1: cfm (ft
3
)
When the unit selection function is
not included,
a read/write to an un-selectable item
is rejected.
1010 0x03F2
0
R/W
CoL
(Selection of display colour)
U8
2
Y
0: rEd (Constantly red)
1: Grn (Constantly green)
2: 1SoG
(OUT1 turns green at ON)
3: 1Sor
(OUT1 turns red at ON)
4: 2SoG
(OUT2 turns green at ON)
5: 2Sor
(OUT2 turns red at ON)
Setting of display colour
1020 0x03FC
0
R/W
NorP
(Selection of switch output
PNP/NPN)
U8
1
Y
0: NPN
1: PNP
Setting the switch output
1030 0x0406
0
R/W
Change by FUNC
U8
0
Y
0: Aout (Analogue output)
1: in (Exterior input)
FUNC terminal function setting
1070 0x042E
0
R/W
Reference condition
U8
0
Y
0: std
(Standard condition)
1: nor
(Normal condition)
1210 0x04BA
1
R/W
OUT
1
se
tt
in
g
oUt1
(Selection of output
mode)
U8
0
Y
0: HYS
(Hysteresis)
1: Wind
(Window comparator)
2: AC
(Accumulated output)
3: PLS
(Accumulated pulse)
4: Err (Error output)
5: oFF (Output OFF)
2
R/W
1ot
(Selection of output
type)
U8
0
Y
0: 1_P (Normal output)
1: 1_n (Reverse output)
Setting of OUT1 output normal and
reserved output
1220 0x04C4
1
R/W
P_1 (n_1)
(Selection of output
set value)
S16 2000
Y
Setting range
Refer to "Settable
range list".
(Page
Setting of OUT1 output set value
(Hysteresis)
2
R/W
H_1
(Setting of OUT1
hysteresis)
U16
200
Y
Setting range
Refer to "Settable
range list".
(Page
Setting of OUT1 hysteresis
(Hysteresis)
3
R/W
P1L (n1L)
(Lower limit of
window comparator)
S16 1200
Y
Setting range
Refer to "Settable
range list".
(Page
Setting of OUT1 output set value
(Lower limit of window comparator)
4
R/W
P1H (n1H)
(Upper limit of
window comparator)
S16 2400
Y
Setting range
Refer to "Settable
range list".
(Page
Setting of OUT1 output set value
(Upper limit of window comparator)
5
R/W
WH1
(Window comparator
hysteresis)
U16
400
Y
Setting range
Refer to "Settable
range list".
(Page
Setting of OUT1 hysteresis
(Window comparator)
6
R/W
dt1
(Delay time)
U16
0
Y
Settable values
0x0000 to 0x1770
(0 to 6000)
Setting of OUT1 delay time
10 ms increment