-40-
No.PF
※※
-OMG0010-G
●
Analogue output
A
B
Voltage output
1 V
5 V
Current output
4 mA
20 mA
Model
Rated flow range
Min.
Max.
PF2A703H
150 NL/min
3000 NL/min
5.5 CFM
106.0 CFM
PF2A706H
300 NL/min
6000 NL/min
10.5 CFM
212.0 CFM
PF2A712H
600 NL/min
12000 NL/min
21.0 CFM
423.5 CFM
: Analogue output is based on the rated flow range at normal condition.
Displayed flow range is based on standard condition.
Therefore, the range of rated flow and the displayed flow are different..
At analogue output mode, the output analogue value varies by switching the mode (normal condition
↔ standard condition).
Use the formula below when the analogue output is used during standard condition.
Flow rate at normal condition ÷ 0.927 = Flow rate of standard condition