background image

No.PF

※※

-OMG0010-G 

 

 

 

 

 

 

 

 
 

PRODUCT NAME 

 

Digital Flow Switch 

(Integrated display type) 

 

MODEL / Series / Product Number 

 

PF2A7##H 

 

 

 

 

 

 

 

 
 

 

 

 

 

 

 

 

 

 

Summary of Contents for PF2A703H

Page 1: ...No PF OMG0010 G PRODUCT NAME Digital Flow Switch Integrated display type MODEL Series Product Number PF2A7 H...

Page 2: ...on mode 20 F_0 Initialize mode 21 F_1 Selection of display mode 22 F_2 Unit selection function 23 F_3 Selection of output mode 24 F_4 Selection of switch operation 25 F_5 Key lock function 26 F_6 Inpu...

Page 3: ...equipment failure when configuring the equipment 2 Only personnel with appropriate training should operate machinery and equipment The product specified here may become unsafe if handled incorrectly T...

Page 4: ...the failure of the product 3 Prior to using SMC products please read and understand the warranty terms and disclaimers noted in the specified catalog for the particular products 2 Vacuum pads are exc...

Page 5: ...the product can result Verify the specifications before use Do not operate in an atmosphere containing flammable explosive or corrosive gas Fire or an explosion can result This product is not designed...

Page 6: ...on can result Insufficient supply voltage may not drive a load due to a voltage drop inside the product Verify the operating voltage of the load before use Do not exceed the specified maximum allowabl...

Page 7: ...dicated on the product label for installation and piping Remaining air can cause inability to measure accurately Do not mount the body with the bottom facing upwards Retention of air can cause inabili...

Page 8: ...Wire correctly Incorrect wiring can damage the product Do not perform wiring while the power is on Otherwise damage to the internal parts can result causing malfunction Do not route wires and cables...

Page 9: ...s CE marked but not immune to lightning strikes Take measures against lightning strikes in the system Do not use the product in areas that are exposed to vibration or impact Otherwise failure or malfu...

Page 10: ...settings can cause operational failure Refer to page 18 Outline of setting During the initial setting and any subsequent flow rate setting the product will switch the output according to the existing...

Page 11: ...e Lead wire is not assembled with the product but shipped together Accessories Part number If an accessory is required separately order using the following part numbers Part number Description Remarks...

Page 12: ...tting mode and error indication Indicator LED reference condition Indicates the reference condition selected LED is ON Red when standard condition is selected Indicator LED output Indicates the output...

Page 13: ...ll span or full scale and indicates varied analogue output range at rated value For example when analogue output is 1 to 5 V F S 5 V 1 V 4 V ref 1 F S 4 V x 1 0 04 V H Hysteresis The difference betwee...

Page 14: ...type that has only 2 conditions ON or OFF In the ON condition an indicator LED will turn on and any connected load will be powered In the OFF condition there will be no indicator LED and no power is s...

Page 15: ...and Installation Installation Never mount the product in a location that will be used as a foothold The rotation angle of the monitor is 270o in steps of 90o Rotating the display part with excessive f...

Page 16: ...Connecting the piping Ensure that the metal piping attachments are tightened to the required torque refer to the table below If the tightening torque is exceeded the product can be broken If the tigh...

Page 17: ...an be prevented by inserting a noise filter such as a line noise filter and ferrite core between the switch mode power supply and the product or by using a series power supply instead of a switch mode...

Page 18: ...ut Analogue 4 to 20 mA type PF2A7 H 29 Max 30 V 80 mA Internal voltage drop 1 V or less 28 Analogue output 1 to 5 V Output impedance 1 k 29 Analogue output 4 to 20 mA Max Load impedance 250 PNP 1 outp...

Page 19: ...accumulated flow is displayed The instantaneous flow value can be displayed by pressing the button The display digits for accumulated flow can be changed by pressing the button unit flashes Press the...

Page 20: ...eresis mode Set point 1 Set point 2 Window comparator mode Accumulated flow Accumulated output mode Non Reverse output Upper digits Middle digits Lower digits Reverse output Upper digits Middle digits...

Page 21: ...Selection of display mode d_1 Display instantaneous flow Page 22 F_2 Unit selection function 1 U_1 L min Page 23 F_3 Selection of output mode oU1_0 Instantaneous output mode Page 24 Input of Set point...

Page 22: ...of display mode Refer to page 22 Unit selection function Refer to page 23 Operate only the product with unit selection function Press the button Selection of output mode Refer to page 24 Press the bu...

Page 23: ...ction of display mode Select the display of instantaneous flow or accumulated flow Press the button for select d_1 display instantaneous flow d_2 display accumulated flow Press the button Press the bu...

Page 24: ...etting of unit selection function is completed Return to measurement mode Setting of unit selection function is completed Move on to F_3 Selection of output mode Flow specification when U_2 is selecte...

Page 25: ...required referring to the list of outputs page 19 Press the button for select oU1_0 Instantaneous output mode oU1_1 Accumulated output mode oU1_2 Accumulated pulse output mode Press the button Press...

Page 26: ...Selection of switch operation Select the switch you need referring the list of outputs page 19 Press the button for select oU1_n Reverse output oU1_P Non Reverse output Press the button Press the butt...

Page 27: ...d Return to measurement mode Setting of key lock function is completed Move on to F_6 Input of the Set point Operation How to unlock Press the button for 3 seconds or longer in measurement mode to dis...

Page 28: ...of outputs page 19 When Non Reverse output has been selected as the switch operation P_1 is displayed Press the button Input of hysteresis This setting is available when Set point 1 Set point 2 It wi...

Page 29: ...of the Set point Input of the Set value for the lower digits n_3 1 and the current Set value Lower digits are displayed in turn Press the and button to change the value referring to list of outputs pa...

Page 30: ...OMG0010 G When Accumulated pulse output mode is selected No Set value is input F_6 is not displayed in function selection mode The display moves on to the selection of the switch operation in initial...

Page 31: ...c pressure at 20 C 65 R H nor Normal condition Flow display which is converted in atmospheric pressure at 0 C Flow rate in the specification is the value at standard condition If the display unit stan...

Page 32: ...fe will be as follows 4 minutes x 1 million cycles 4 million times approximately 7 6 years Operation Press the and buttons in function selection mode to display F_8 Press the button Accumulated value...

Page 33: ...duct can be returned to the default settings Operation Press the and buttons in function selection mode to display F_0 Press the and buttons simultaneously for 3 seconds or longer The display will cha...

Page 34: ...ng of the product will be retained as it was before a power cut or de energizing The output condition is also basically recovered to that before a power cut or de energizing but may change depending o...

Page 35: ...ion arrow indicated on the product Pulsation in the flow Change to a pump that has less pulsation Install a tank to reduce the pressure fluctuation Change the piping to elastic piping such as rubber t...

Page 36: ...nnected in the wrong direction Install with the mounting direction corresponding to the flow direction arrow indicated on the product Pulsation in the flow Change to a pump that has less pulsation Ins...

Page 37: ...rror The set data has been changed unexpectedly To reset press the button for 6 seconds or longer while the button is pressed Then set all data again The internal circuit could be damaged Stop using a...

Page 38: ...range 0 1 to 1 5 MPa Proof pressure 2 25 MPa Switch output NPN open collector output PNP open collector output Output mode 3 Instantaneous flow output mode hysteresis mode window comparator mode Accu...

Page 39: ...isplay unit is changed from standard ANR to normal nor use the following conversion formula Flow rate at standard condition x 0 927 Flow rate at normal condition 2 If the flow rate is smaller than the...

Page 40: ...39 No PF OMG0010 G Characteristics data Flow characteristics pressure loss PF2A703H PF2A706H PF2A712H...

Page 41: ...23 5 CFM Analogue output is based on the rated flow range at normal condition Displayed flow range is based on standard condition Therefore the range of rated flow and the displayed flow are different...

Page 42: ...2A703H 55 mm 160 mm 40 mm 92 mm 67 mm 55 mm Rc1 NPT1 G1 PF2A706H 65 mm 180 mm 45 mm 104 mm 79 mm 65 mm Rc11 2 NPT11 2 G11 2 PF2A712H 75 mm 220 mm 55 mm 114 mm 89 mm 75 mm Rc2 NPT2 G2 Model H I J PF2A7...

Page 43: ...42 No PF OMG0010 G Lead wire and connector Straight ZS 37 A Lead wire and connector Right angle ZS 37 B Dimensions of rotating monitor part...

Page 44: ...ed in several places E Modified errors in text F Modified errors in text G Modified errors in text September 2017 4 14 1 Sotokanda Chiyoda ku Tokyo 101 0021 JAPAN Tel 81 3 5207 8249 Fax 81 3 5298 5362...