JXCP1-TF2Z197EN
Page 2 of 2
5 Setting
5.1 Initial Setting
•
Appropriate setting is required in order to establish the communication
of the controller (JXCP1) on the PROFINET network.
•
Please refer to the PLC setting software "SIMATIC Manager Version
5.5 (STEP7) for the representative PROFINET master device.
•
The required setting method such as the GSDML file installation varies
depending on which setting software will be used, so if software other
than STEP7 is used, please refer to the operation manual of the
applicable setting software.
In order to move the electric actuator to a specific position, it is necessary
to set up the patterns of operation with a PC using the controller setting
software or by using a teaching box. This set up data will be recorded in
the memory of the controller.
Refer to the Operation Manual on the SMC website (URL:
) for further setting details.
5.2 Configuration
•
A GSDML file and icons file are required to configure the controller.
The latest GSDML file can be downloaded from the SMC website
(URL:
).
6 LED Display
Refer to the table below for the LED status.
Refer to the table below for the LED and controller status
Controller status
LED
PWR
ALM
SF
BF
When power is supplied
Green
LED is
ON
LED is
OFF
-
-
When PROFINET
communication is normal
-
-
LED is
OFF
LED is
OFF
Motor
controller
Controller
alarm
generated
LED is
OFF
Red
LED is
ON
Red
LED is
ON
-
Controller
system error
generated
Green
LED is
ON
Red
LED is
ON
-
-
Writing to
controller
Eeprom
Green
LED is
flashing
-
-
-
Caution
Do not turn OFF the power supply for the controller or connect /
disconnect the cable while data is being written to EEPROM (PWR LED
(green) is flashing).
This is to avoid the possibility of incorrect / corrupt data (step data,
parameter).
7 How to Order
Refer to the catalogue on the SMC website (URL:
) for the How to Order information.
8 Outline Dimensions (mm)
Refer to the drawings / operation manual on the SMC website (URL:
) for outline dimensions.
9 Maintenance
9.1 General Maintenance
Caution
•
Not following proper maintenance procedures could cause the product
to malfunction and lead to equipment damage.
•
Before performing maintenance, turn off the power supply. Check the
voltage with a tester 5 minutes after the power supply is turned OFF.
•
If any electrical connections are disturbed during maintenance, ensure
they are reconnected correctly and safety checks are carried out as
required to ensure continued compliance with applicable national
regulations.
•
Do not make any modification to the product.
•
Do not disassemble the product, unless required by installation or
maintenance instructions.
Caution
•
Maintenance should be performed according to the procedure
indicated in the Operation Manual.
•
When equipment is serviced, first confirm that measures are in place
to prevent dropping of work pieces and run-away of equipment, etc,
then cut the power supply to the system. When machinery is restarted,
check that operation is normal with actuators in the correct position.
Warning
•
Perform maintenance checks periodically.
•
Confirm wiring and screws are not loose. Loose screws or wires may
cause unexpected malfunction.
•
Conduct an appropriate functional inspection and test after completing
maintenance. In case of any abnormalities (if the actuator does not
move, etc.), stop the operation of the system. Otherwise, an
unexpected malfunction may occur and it will become impossible to
ensure safety. Operate an emergency stop instruction to confirm safety.
•
Do not put anything conductive or flammable inside of the controller.
•
Ensure sufficient space around the controller for maintenance.
10 Limitations of Use
10.1 Limited warranty and Disclaimer/Compliance Requirements
Refer to Handling Precautions for SMC Products.
11 Product disposal
This product shall not be disposed of as municipal waste. Check your
local regulations and guidelines to dispose of this product correctly, in
order to reduce the impact on human health and the environment.
12 Contacts
or
importer.
URL:
(Global)
(Europe)
SMC Corporation, Akihabara UDX15F,
4-14-1
, Sotokanda, Chiyoda-ku, Tokyo
101
0021
Specifications are subject to change without prior notice from the manufacturer.
© 2021 SMC Corporation All Rights Reserved.
Template DKP50047-F-085M
LED
Details
PWR
Power supply
status.
OFF
Power is not supplied
Green LED is
ON
Power is supplied
ALM
Controller alarm
status.
OFF
Normal operation
Red LED is
ON
Alarm generated
SF
Controller
status.
OFF
Normal operation
Red LED is
ON
Alarm generated (Linked to
ALM)
BF
PROFINET
communication
status
OFF
PROFINET communication
is established.
Red LED is
flashing
PROFINET communication
is not established.
Red LED is
ON
Both Port1 and Port2 are
not connected.