IDX-OM-Y002
Chapter 3
Transportation
and installation
IDF190D/240D Series
3.2
Installation
3-5
Power supply cable length
Power cable length for the product shall be less than 30m.
Power supply
Connect the power cable and grounding cable to the terminal block.
Wiring procedure
1) Remove the front panel.
2)
Introduce the cable through the grommet with membrane to connect to the terminal block. (refer to
the label on the terminal block)
Do not touch any equipment other than the terminal block during wiring. (Refer to the layout of the
terminal box).
3) Loosen the M4 screw of the terminal block using a screwdriver. Attach the round crimp terminal
(R5.5-4) attached to the power cable and tighten it to the terminal block with the previously loosened
screw.
【
Tightening torque:1.0N
・
m
】
4) Mount the front panel back.
3.2.5.2.
Wiring of signal cable (operation / error / remote operation)
Remove the front panel of the product and connect the signal cable to the terminal block.
Signal cable specification
Prepare the following signal cables:
Signal cable: 20AWG (0.5mm
2
or greater), cable O.D.
Approx. 9mm, 6 cores
Approx. 1.5m of cable is necessary for wiring in the product.
Signal cable length
Signal cable length shall be less than 30m.
Signal cable Connection
Connect the signal cable to the terminal block.
Wiring procedure
1) Remove the front panel.
2) Introduce the cable through the grommet with membrane to connect to the terminal block. (refer to
the label on the terminal block)
Do not touch any equipment other than the terminal block during wiring. (Refer to the layout of the
terminal box)
3) Loosen the M4 screw of the terminal block using a screwdriver. Attach the round crimp terminal
(R1.25-4) attached to the signal cable and tighten it to the terminal block with the previously
loosened screw. (Tightening torque: 1.0 N
・
m)
Terminal width
:
9.9mm
アース
お客様接続側
異 常
信 号
運 転
信 号
24
23
6
5
22
21
電源
遠 隔
運 転
PE
L3
L2
L1
端子台の配置図
Remote
operation
Gr
o
u
n
d
(to be connected to the user's equipment)
RUN
signal
Power
supply
Error
signal