HRX-OM-R039
Chapter 5 Display and setting of various functions
HRSE Series
5.6
Alarm customize function
5-13
5.6 Alarm customize function
5.6.1
Alarm customize function
The operation and the threshold when alarm signal is output can be
customized. Customers should set them depending on their applications.
The alarms below can be customized.
●AL03
Circulating fluid discharge temp. rise (Refer to Table 5.6-3 and Table 5.6-4)
Operation: When this alarm signal is output, user can choose to
stop/continue operation, or not to detect this alarm.
"Operation continue" is default setting.
Threshold change: Temp. setting at which the alarm is generated can be
changed, and also, the alarm generating conditions can be set.
“35
o
C" is default setting.
●AL04
Circulating fluid discharge temp. (Refer to Table 5.6-5 and Table 5.6-6)
Operation: When this alarm signal is output, user can choose to
stop/continue operation, or not to detect this alarm.
"Operation continue" is default setting.
Threshold change: Temp. setting at which the alarm is generated can be
changed, and also, the alarm generating conditions can be set.
“1
o
C" is default setting.
5.6.2
Alarm customize function setting and checking
The table below explains the setting items of the alarm customize function
and the initial values.
Table 5.6-1
List of set alarm customize function
(
1/2
)
Display
Item
Contents
Initial value
(Default setting)
Changing of circulating
fluid
discharge
temperature rise
Set the operation when alarm No. AL03
"circulating fluid discharge temperature rise" is
generated.
A.RUN
Detection temperature for
circulating fluid discharge
temperature rise
Sets the detection temperature for the alarm of
alarm NO. AL03 "circulating fluid discharge
temperature rise ".
Alarm signal is generated when the temperature
becomes higher than this temperature.
35
o
C
Changing of circulating
fluid
discharge
temperature drop
Set the operation when alarm No. AL04"
circulating fluid discharge temperature drop
“is
generated.
A.RUN
Detection
temperature for
circulating fluid discharge
temperature drop
Sets the detection temperature for the alarm of
alarm NO. AL04 "circulating fluid discharge
temperature drop ".
Alarm signal is generated when the temperature
becomes lower than this temperature.
1
o
C
Temperature alarm
Monitoring method
One alarm monitoring method can be selected
from four methods for AL04 "Detection temp for
the circulating fluid discharge temp. increase"
and AL06 "Detection temp. for circulating fluid
discharge temp. drop".
0