HRX-OM-W058
Chapter 9 Documents
HRS-R Series
9.1
Specifications List
9-3
9.1.3
Communication specifications
Contact input/output
Table 9-3 Specifications List
Item
Specification
Connector type (for this product)
MC1,5/12-GF-3,5
For option B:
DFK-MC1,5/12-GF-3,81
Input signal
Insulation system
Photo coupler
Rated input Voltage
DC24V
Operating voltage range
DC21.6V to 26.4V
Rated input current
5mA TYP
Input signal
4.7k
Ω
Contact output signal
Rated load current
AC48V or less /DC30V or less
Maximum load current
AC/DC500mA (Resistance load)
Minimum load current
DC5V 10mA
Output voltage
DC24V±10% 0.5A MAX
Circuit structure diagram
*1 The pin numbers and output signals can be set by user. For details, refer to the [5.19 Communication function].
*2 When using with optional accessories, depending on the accessory, the allowable current of 24 VDC devices will be reduced.
Refer to the operation manual of the optional accessories for details.
0.5A MAX
*2
Settings at the time of
shipment from the factory
*1
(Users can modify the
settings.)
4.7k
Ω
This product
Your system
I
n
te
rn
a
l c
irc
u
it
DC24V
Alarm signal
10
6
Run/stop signal
Run status signal
Remote signal
12
11
24VCOM
9
8
7
5
4
3
2
1
Default unsetting
DC24V output
24VCOM output
1k
Ω
4.7k
Ω
1k
Ω