HRX-OM-W058
Chapter 6 Option
・
Optional Accessories
HRS-R Series
6.4
Option T [High-pressure pump]
6-3
6.4 Option T [High-pressure pump]
6.4.1
Option T [High-pressure pump]
With option T (high pressure pump mounted), the discharge pressure is
raised.
The high pressure pump uses a mechanical seal.
Thermo Chiller makes AL28 alarm when driving time is passed a
recommended preventive maintenance hours. Please contact to service
center to ask for maintenance of the pump and mechanical seal.
Applicable model
-
-20-T-R
Pump
Rated flow (50/60 Hz)
Note 1),2)
L/min
10 (0.35 MPa) /14 (0.35 MPa)
Maximum flow rate (50/60 Hz)
L/min
17 / 20
Maximum pump head (50/60 Hz)
m
70
Output
W
610
Recommended earth leakage breaker capacity
A
15
Cooling capacity
Note 3)
W
The cooling capacity reduces approximately 300 W
from the value in the catalog
Note 1) The capacity at Thermo-chiller outlet.
Note 2) Required minimum flow rate for cooling capacity or maintaining the temperature stability.
Note 3) Cooling capacity decreasing due to bigger pump motor.
6.5 Option V [Stainless steel enclosure]
6.5.1
Option V [Stainless steel enclosure]
With option V , the materials of enclosures are changed to stainless steel.
Enclosures: Front panel, Right side panel, Left side panel, Rear panel,
upper panel and bottom base.