HRX-MM-N007
Chapter 4 Service Procedure
4.5 Replacement Procedure
HRS Series
4-38
Be sure to shut off the breaker of the facility power supply (the user’s
machine power supply) before replacement work.
4.5.11 Replacement of tank
<
HRS
-A/W-
>
Table 4-18 Part number of service parts (Tank)
Description
Part number
Tank
HRS-S0025
Removal
1.
Discharge the circulating fluid referring the 4.2.2 Discharge of the circulating fluid and
facility water.
2.
Remove the upper panel, the panels on both sides and the front panel referring the 4.2.1
Removal and the mounting of the panel.
3.
Remove the hose clamp and remove hose A and hose B.
4.
Remove the level switch pin [LS1] (two red lines) from the main board.
[Tips]
Use “57031-6000” of MOLEX for removing.
Our part no.
:
HRS-S0056
5.
Remove the
tank.
Fig. 4.5-22 Removal of tank
4.
Remove
the
pin
Tank lid
3.
Hose A
3.
Hose B
Grommet
Main board
5.
Tank
Hose clamp