HRX-OM-W069
Chapter 3 Serial communication
HRL Series
3.13
Register Map
3-23
3.13.9
Operation instruction
Name
Operation instruction
Bit
15 14 13 12 11 10
9
8
7
6
5
4
3
2
1
0
Bit
Name
Explanation
0
Operation Start Command
Operation Start /Stop
0= Operation Stop
1= Operation Start
1
Mode request flag
Mode request
0= None
1= Yes
2
Alarm reset flag
Alarm reset
0= None
1= Yes
3 to15 None
-
Operation Start Command
SERIAL mode, you can control the operation start / stop of this product. However,
this function is invalidated when the setting of "DIO Run / Stop" is ON on the touch
panel.
Mode request flag
The mode request flag can be switched to the SERIAL mode is changed from 0 to 1.
After that, even if it changes to 0, it keeps SERIAL mode.
(
For details, Refer to
”)
Alarm reset flag
Alarm reset can be performed by changing the alarm reset flag from 0 to 1 in
SERIAL mode.
3.13.10
Data instruction
By setting the data instructions to display the data that you selected in
each data display 1, 2, 3, 4.
The types of data that can be displayed are shown below.
Data display 1 displays data of the type instructed in data instruction 1
(data instruction 0-3 bits), data display 2 data instruction 2 (data
instruction high 5-7 bits), data display 3 data instruction 3 (data
instruction high Data display 4 displays data of the type specified in
data indication 4 (upper 12-15 bits of data indication).