background image

HRX-OM-Y120 

Chapter 3 Serial communication 

3.8

 

Message configuration 

HRL Series 

 
 

3-8 

Table 3.8-1 ASCII mode message frame 

a)Start 

b)Slave 

Address 

c)Function 

d)Data 

e) Checksum 

(LRC) 

f)End 

[:] 

XX 

XX 

XX 

XX 

XX 

 

XX 

XX 

XX 

[CR] 

[LF] 

 

a) Start 

The start of the message. [:](3Ah) (ASCII) 

b) Slave Address 

This is a number to identify this product. 

“1" is the default setting. 

This can be changed by the touch panel. 

c) Function

 

(Refer to 

“3.9 

Function codes

)

 

Command is assigned.

 

d) Data 

Depending on the function, the address and the number of the 
register, the value of reading/writing are assigned.

 

e) LRC 

LRC method

 

Refer to 

‘’3.10.1 

LRC(ASCII)

’’.

 

f) END 

The end of the message. [CR](0Dh)

[LF](0Ah)

 

 

2)

 

  RTU mode frame 

RTU mode starts from and ends with at least 3.5 characters of silent interval. Silent   
interval is indicated by T1-T2-T3-T4. 

 

Table 3.8-2 RTU mode message frame

 

a)Start 

b)Slave 

Address 

c)Function 

d)Data 

e) Checksum 

(CRC) 

f)End 

T1-T2-T3-T4

 

XX 

XX 

XX 

  XX 

XX 

XX 

T1-T2-T3-T4 

 

a) Start 

In Modbus RTU mode, message frames are separated by a silent interval 
(non-communication time). At least 3.5 characters of silent interval are necessary 
at the beginning and the end of the communication frame.

 

b) Slave Address 

This is a number to identify this product. 

“1" is the default setting. This can be 

changed by the touch panel. 

c) Function (Refer to 

“3.9 Function codes”

Command is assigned. 

 

 

 

Summary of Contents for HRL100-A*-20 Series

Page 1: ...nction Thermo chiller Air Cooled refrigerated type Water Cooled refrigerated type HRL100 A 20 40 HRL100 W 40 HRL200 A 20 40 HRL200 W 40 HRL300 A 20 40 HRL400 A 40 Keep this manual available whenever necessary 2022 SMC CORPORATION All Rights Reserved ...

Page 2: ...installation and operation of the product Only people who understand the basic operation of the product through this manual or who performs installation and operation of or have basic knowledge about industrial machines are allowed to work on the product This manual and other documents do not constitute a contract and will not affect any existing agreements or commitments It is strictly prohibited...

Page 3: ... 1 Contact output signal 1 to 3 2 10 2 4 2 Contact output signal 4 to 6 2 11 2 5 Analog output signal 2 14 Chapter 3 Serial communication 3 1 3 1 Precautions wiring communication 3 1 3 2 Connected explanation 3 1 3 3 Communication specification 3 2 3 4 Modbus communication function 3 3 3 5 Precautions for communication 3 4 3 5 1 Precautions after wiring and before communication 3 4 3 5 2 Precautio...

Page 4: ... Connected explanation 5 2 5 4 Communication specification 5 3 5 5 Modbus TCP communication function 5 3 5 6 Precautions for communication 5 4 5 6 1 Precautions after wiring and before communication 5 4 5 6 2 Precautions for communicating 5 4 5 7 Setting method 5 5 5 7 1 IP Address Setting 5 6 5 7 2 Setting of subnet mask and default gateway 5 7 5 8 Communication sequence 5 8 5 9 Message configura...

Page 5: ...HRX OM Y120 Contents HRL Series 5 12 13 Control board program number 5 17 5 12 14 Control board program version 5 17 5 12 15 Display program number 5 17 5 12 16 Display program version 5 17 ...

Page 6: ...HRX OM Y120 Contents HRL Series ...

Page 7: ... communication This product is equipped with a terminal which runs stops the product by remote control and a terminal which can pick up alarm signals The terminals can be changed depending on the customer s application Serial communication Modbus standard Protocol Serial communication RS 485 RS232C enables remote control of run start of the product temperature setting and details of product condit...

Page 8: ...e at the touch panel Set the operation mode to DIO To display the DIO SERIAL Run stop and circulating fluid temperature setting are possible with the serial communication RS 232C RS 485 Set the operation mode to SERIAL To display the SERIAL DIO Run Stop Run stop by contact input Set circulating fluid temperature by serial communication Set to SERIAL mode and set DIO Run Stop in Serial Setting to O...

Page 9: ... switch can be connected 1 2 Change of operation mode There are the following methods to change the operation mode Change by touch panel Change by mode request About mode request The mode request is the ability to change the operation mode by the contact input or serial communication and Ethernet communication When switching from OFF to ON for both contact input serial communication and Ethernet c...

Page 10: ...lect the LOCAL in the touch panel Operation mode Ethernet communication Mode request flag Ethernet LOCAL DIO SERIAL DIO Ethernet SERIAL Ethernet Contact input3 Mode request signal Serial communication Mode request flag Operation mode Ethernet communication Mode request flag Fig 1 1 Mode switching by the mode request Standard Fig 1 2 Mode switching by the mode request ON state mixed ...

Page 11: ...n port In the lower left of the electrical component box is used for communication Fig 1 3 shows the location of the communication port Fig 1 3 Communication port Contact input output signal connector D sub 25 female pin socket type Serial communication connector D sub 9 female pin socket type 13 1 25 14 5 1 9 6 RJ45 ...

Page 12: ... screens Fig 1 4 Communication setting touch panel flow Menu 1 Communication error AL34 Detection of contact input signal Setting for alarm AL30 and AL31 3 Analog output setting 4 Setting for contact input signal 1 to 3 2 Serial communication setting 5 Setting for contact output signal 1 to 3 6 Setting for contact output signal 4 to 6 Various screens 7 Setting for Ethernet communication ...

Page 13: ...ase prepare according to 3 2 Connected explanation In order to avoid malfunction do not connect to any place other than those shown in 3 2 Connected explanation Power supply To use the power of the product the total load current must be 200mA or less Signal content Contact input 1 Contact input 2 Contact input 3 Mode request signal only momentary Contact output 1 Output operation status RUN STOP s...

Page 14: ...ating voltage range DC21 6V to 26 4V Rated input current 5mA TYP Input impedance 4 7kΩ Contact output signal 1 2 3 4 5 6 Rated load voltage AC48V or less DC30V or less Signal of operating status Alarm signal TEMP READY signal etc 2 Maximum load current AC DC 800mA or less 1 Minimum load current DC5V 10mA Analog output signal 1 2 Output voltage range 0V to 10V CH1 Circulating fluid discharge temper...

Page 15: ...lating fluid electric conductivity signal 1 11 Analog output signal 1 Output CH2 Circulating fluid discharge temperature signal 1 12 None Can not connect 3 13 None Can not connect 3 14 24 COM output Common of contact input signal Output 15 Common of contact output signal 1 2 3 4 5 Output 16 Contact input signal 2 Input External switch signal 1 17 None Can not connect 3 18 Common of contact output ...

Page 16: ...ntary Run Stop Operation mode request Warning when an alarm occurs OFF Fault when an alarm occurs OFF Operation ON Contact output 6 OFF 2 DC24V DC 24V input EXT DC24V EXT 24COM Power supply Analog output 2 CH2 Circulating fluid electric conductivity External switch 24COM output Contact output 1 5 common Contact output 6 common Analog output1common Analog output 2 common When using this product s p...

Page 17: ... type and form The type of contact input signal can be set from the 1 4 Touch panel flow Refer to 4 Contact input signal form screen Following items can be set for contact input signal 1 and 2 Contact type selects N O A contact or N C B contact Signal form selects ALT alternate or MT momentary Signal type selects OFF disabled external switch external switch signal or run stop run stop signal Run r...

Page 18: ...ff Disabled External Switch External switch signal Run Stop 1 Run stop signal Run 2 Run signal 2 Input 2 Contact input signal 2 Contact type 1 A contact normally open B contact normally closed Signal form 1 Alternate Momentary Signal type Off Disabled External Switch 1 External switch signal Stop 2 Stop signal 3 Input 3 Contact input signal 3 3 Contact type 1 A contact normally open B contact norm...

Page 19: ...al Signal type Alternate Stop signal Signal type Alternate Digital input signal 1 is for Run signal Signal type Alternate digital input signal 2 is for stop signal Signal type Alternate Stop signal becomes valid when both signals are turned ON 1 The product starts operation when the contact input signal 1 is turned ON 2 The product stops operation when the contact input signal 2 is turned ON 3 The...

Page 20: ...s allows reading and monitoring the contact signal from an external switch When inputting an external switch signal to the contact input select External Switch external switch signal for the type of contact input signal Refer to 2 3 1 Setting of contact input signal type and form If an input from an external switch is detected it can be generated as an alarm Options to select continuous monitoring...

Page 21: ...e operation of this product when an alarm occurs by the contact input signal WRN Continue operation of the product when an alarm occurs FLT Stop operation of this product when an alarm occurs Set Delay time Off Detect time and Operation at alarm occurrence of external switch signal from 1 4 Touch panel flow Refer to 1 Communication error AL34 contact input signal detection alarm AL30 AL31 setting ...

Page 22: ...rm Off Detect 0 to 10sec 0sec Operation stops during alarm 3 Digital Input 2 Alarm AL31 Detection of contact input 2 signal Disabled Delay 0 to 300sec 0sec Operation continues during the alarm Off Detect 0 to10sec 0sec Operation stops during alarm By default 2 4 Contact output signal There are 6 contact output signals The setting of the contact output signal is done by the 5 Contact output signal ...

Page 23: ...d By default 2 4 2 Contact output signal 4 to 6 Contact output signal 4 to 6 can be set to signal type contact form A signal type for contact output signal 4 to 6 can be selected by the customer Refer to Table 2 4 3 Signal type for contact output signals 4 to 6 Table 2 4 2 Setting of contact output signal 4 to 6 No Indication Item Signal type Contact type 1 Output 4 Function Contact output signal ...

Page 24: ...currence closed Selected alarm occurrence open Selected maintenance reminders occurred open Maintenance reminders status signal Anti freezing setting status signal Warming up setting status signal Pass through signal of the contact input signal 1 Pass through signal of the contact input signal 2 16 Digital Input 2 17 Mode Request Input Selected maintenance reminders occurred closed 19 Select Maint...

Page 25: ... sensor AL22 CH2 High Press Error CH2 abnormal rise in circulating fluid discharge pressure AL23 CH2 High Press CH2 circulating fluid discharge pressure rise AL24 CH2 Low Press CH2 circulating fluid discharge pressure drop AL25 CH2 Low Press Error CH2 abnormal drop in circulating fluid discharge pressure AL26 CH2 Flow Sensor CH2 failure of circulating fluid discharge flow sensor AL27 CH2 High Elec...

Page 26: ...CH2 Mechanical Seal CH2 Mechanical Seal mentenance 1 Refer to Operation Manual Installation Operation 2 In the case of option D1 CH1 with electrical conductivity control to display 3 In the case of option T3 CH2 High Pressure Pump Mounted to display 4 In the case of air cooled refrigerated type to display 2 5 Analog output signal The product has two analog outputs Setting of the analog output sign...

Page 27: ...ating fluid discharge temperature 0ºC to 100ºC 0 to 10 0 V 1 CH2 circulating fluid discharge temperature 0ºC to 100ºC 0 to 10 0 V CH2 circulating fluid electrical conductivity 0 1 to 50 0 μS cm 0 02 to 10 0 V CH1 circulating fluid discharge temperature 0ºC to 100ºC 0 to 10 0 V 2 CH1 circulating fluid electrical conductivity 0 1 to 50 0 μS cm 0 02 to 10 0 V CH2 circulating fluid discharge temperatu...

Page 28: ...HRX OM Y120 Chapter 2 Contact input output communication Analog output communication 2 5 Analog output signal HRL Series 2 16 ...

Page 29: ...t connects the product and customer system is not included with the product Please prepare a cable referring to 3 2 Connected explanation In order to avoid malfunction do not connect to any place other than those shown in 3 2 Connected explanation 3 2 Connected explanation Fig 3 1 shows the wiring when RS 485 is selected as the communication standard Fig3 2 shows the wiring when RS 232C is selecte...

Page 30: ...or connection 3 3 Communication specification Table 3 3 1 Serial communication specification Item Specification Connector type for the product D sub9P type Female connector Standard Select from EIA RS 485 RS 232C Circuit type Half duplex Half duplex Transmission type Start stop Protocol Modbus terminal 1 Terminal resistance None Default setting 1 Refer to Modicon Co protocol specifications PI MBUS...

Page 31: ... Default setting 3 4 Modbus communication function Modbus protocol is a communication protocol developed by Modicon It is used to communicate with a PC or PLC Register content is read and written by this communication protocol This communication has the following features Controls run stop Sets and reads the circulating fluid set temperature Reads the circulating fluid discharge temperature Reads ...

Page 32: ...t messages in series wait for 100 msec or longer after receiving a response message from the product before sending the next message Retry resend request message The response may not be returned due to noise If no message is returned 1sec after sending a request message resend the request message If necessary send a read request message to check if it was written correctly Message to notify the co...

Page 33: ...ess 1 to 32 Select from 1 to 32 1 5 DIO Run Stop 1 Run stop by contact input Disabled Enabled 6 Communication Status Communication status 2 0000 Displays the communication status 1 Run stop operation of the product is carried out by the contact input signal and by reading writing the change in set value of circulating fluid temperature and operation status by serial communication 2 It is a functio...

Page 34: ...ustomer s equipment 0081 The slave addresses set for this product and customer s device are different 0041 CRC 1 does not match in the RTU settings 0021 LRC 1 does not match in the ASCII settings 00XX 2 Mismatched communication settings Baud Rate parity number of data bits etc or very short message intervals from customer equipment 0000 3 Bad wiring or no message sent from customer equipment 1 CRC...

Page 35: ...ative response No response No response is returned when there is an error in slave address specification or Checksum LRC CRC 3 8 Message configuration 3 8 1 Message frame The message configuration is shown below The communication of this product uses 2 transmission modes ASCII or RTU 1 ASCII mode frame For ASCII mode the message starts with ASCII characters 3Ah and ends with CR LF 0Dh 0Ah A respon...

Page 36: ...e LRC LRC method Refer to 3 10 1 LRC ASCII f END The end of the message CR 0Dh LF 0Ah 2 RTU mode frame RTU mode starts from and ends with at least 3 5 characters of silent interval Silent interval is indicated by T1 T2 T3 T4 Table 3 8 2 RTU mode message frame a Start b Slave Address c Function d Data e Checksum CRC f End T1 T2 T3 T4 XX XX XX XX XX XX T1 T2 T3 T4 a Start In Modbus RTU mode message ...

Page 37: ... Writing registers 1 3 16 10h preset multiple registers Writing multiple registers 1 Broadcast is not supported 3 10 Checksum calculation method 3 10 1 LRC ASCII LRC checks the content of the message other than of START and CR LF of END The sending side calculates and sets The receiving side calculates based on the received message and compares the calculation result with the received LRC The rece...

Page 38: ...lusive OR the first byte of the transmitted message with the value in 1 3 Shift the result of 2 by one bit toward the least significant bit and fill a zero into the most significant bit position 4 If the least significant bit was a 1 exclusive OR the result of 3 with A001h Example 1 If the least significant bit was a 0 no exclusive OR takes place 5 Repeat 3 to 5 until eight shifts have been perfor...

Page 39: ...00EAh No Classification Contents Result 1 CRC message for calculation 0106000B00FE 2 Calculation Perform 1 to 4 for the 1st value 0001h and then perform 5 807Eh 3 Perform 6 for 2nd value 0006h and then perform 5 2280h 4 Perform 6 for 3rd value 0000h and then perform 5 A023h 5 Perform 6 for 4th value 0040h and then perform 5 29E0h 6 Perform 6 for 5th value 0000h and then perform 5 8828Eh 7 Perform ...

Page 40: ...uctivity 20 0uS cm CH1 Circulating fluid discharge pressure 45MPa CH2 Circulating fluid discharge pressure 0 50MPa CH1 Circulating fluid flow rate 45 0LPM CH2 Circulating fluid flow rate 10 0LPM Data display 1 to 4 non selection all 0 Status flag during operation CH1 CH2 TEMP READY status Alarm flag 1 to 3 no alarm 1 0 is displayed except for option D1 Request message 010400300010 Field name Examp...

Page 41: ...ation of 0034h CH1 Circulating fluid discharge pressure 0x002D 0 0 2 D 0x00 0x2D Information of 0035h CH2 Circulating fluid discharge pressure 0x0032 0 0 3 2 0x00 0x32 Information of 0036h CH1 Circulating fluid flow rate 0x01C2 0 1 C 2 0x01 0xC2 Information of 0037h CH2 Circulating fluid flow rate 0x0064 0 0 6 4 0x00 0x64 Information of 0038h Data display 1 0x0000 0 0 0 0 0x00 0x00 Information of ...

Page 42: ...01 Function 0x06 0 6 0x06 Head address of specified register 0x0042 0 0 4 2 0x00 0x42 Information written to 0042h Mode request 0x0002 0 0 0 2 0x00 0x02 Checksum ASCII LRC RTU CRC B 5 0xA8 0x1F Trailer CR LF None Total quantity of byte 17 8 Response message 010600420002 Field name Example HEX ASCII mode character data RTU mode binary data Header None Slave Address 0x01 0 1 0x01 Function 0x06 0 6 0...

Page 43: ...register 0x0040 0 0 4 0 0x00 0x40 Quantity of register to write 0x0003 0 0 0 3 0x00 0x03 Quantity of byte to read 0x06 0 6 0x06 Information written to 0040h CH1 Circulating fluid set temperature 0x00EB 0 0 E B 0x00 0xEB Information written to 0041h CH2 Circulating fluid set temperature 0x015D 0 1 5 D 0x01 0x5D Information written to 0042h Operation stop flag 0x0001 0 0 0 1 0x00 0x01 Checksum ASCII...

Page 44: ...ative acknowledgment message frame in RTU Start Slave Address 1 Function 2 Error Code CRC End T1 T2 T3 T4 1 XX XX XX XX XX XX T1 T2 T3 T4 1 Silent interval for 3 5 characters 1 Function Assign the value consisting of the request function code hexadecimal value plus 80h Example 1 ASCII mode Received function code 04 0000 0100 ASCII code 30h 34h Abnormal function code 84 1000 0100 ASCII code 38h 34h...

Page 45: ...n 0x04 0 4 0x04 Head address of register out of range 0x0100 0 1 0 0 0x01 0x00 Quantity of register to read 0x0007 0 0 0 7 0x00 0x07 Checksum ASCII LRC RTU CRC F 3 0xB0 0x34 Trailer CR LF None Total quantity of byte 16 8 Response message 018402 Field name Example HEX ASCII mode character data RTU mode binary data Header None Slave Address 0x01 0 1 0x01 Function 03h 80h 0x84 8 4 0x84 Error Code Spe...

Page 46: ... Hexadecimal number 8000h to 7FFFh 0 1LPM dig 0037h CH2 Circulating fluid flow rate Decimal number 3276 8 to 3276 7LPM Hexadecimal number 8000h to 7FFFh 0 1LPM dig 0038h Data display 1 Follow the data instructions 1 0039h Data display 2 Follow the data instructions 1 003Ah Data display 3 Follow the data instructions 1 003Bh Data display 4 Follow the data instructions 1 003Ch Status flag Refer to 3...

Page 47: ...rge temperature which is displayed on the touch panel Offset temperature is displayed if offset function is set 3 13 2 Circulating fluid electrical conductivity Notifies the circulating fluid electrical conductivity CH2 only 3 13 3 Circulating fluid discharge pressur To notify the circulating fluid discharge pressure of the product 3 13 4 Circulating fluid flow rate To notify the circulating fluid...

Page 48: ...ance status 0 Not generated 1 Generated 4 CH1 Completion of preparation TEMP READY flag Completion of preparation TEMP READY status 0 Condition isn t formed 1 Condition is formed 5 CH1 Completion of preparation TEMP READY flag Completion of preparation TEMP READY status 0 Condition isn t formed 1 Condition is formed 6 TEMP OUT flag TEMP OUT status 0 Condition isn t formed 1 Condition is formed 7 N...

Page 49: ...11 CH1 TEMP READY alarm 12 CH2 abnormal rise of circulating fluid temperature 13 CH2 circulating fluid temperature rise 14 CH2 circulating fluid temperature drop 15 CH2 TEMP READY alarm Alarm flag 2 0 CH1 abnormal rise in heat exchanger inlet temperature 1 CH1 failure of circulating fluid discharge pressure sensor 2 CH1 circulating fluid discharge pressure rise 3 CH1 circulating fluid discharge pr...

Page 50: ... 0 None 0 1 Ambient temperature Decimal number 327 6 to 327 6 Hexadecimal number F334h to 0CCCh 0 1 dig 2 External tuning temperature Decimal number 327 6 to 327 6 Hexadecimal number F334h to 0CCC 0 1 dig 3 CH1 heat exchanger inlet temperature Decimal number 327 6 to 327 6 Hexadecimal number F334h to 0CCCh 0 1 dig 4 Notice for maintenance Occurrence status of each maintenance 0 Not occurred 1 Occu...

Page 51: ...e request flag can be switched to the SERIAL mode is changed from 0 to 1 After that even if it changes to 0 it keeps SERIAL mode For details Refer to 1 2 Change of operation mode Alarm reset flag Alarm reset can be performed by changing the alarm reset flag from 0 to 1 in SERIAL mode 3 13 10 Data instruction By setting the data instructions to display the data that you selected in each data displa...

Page 52: ...ure refrigerant circuit Data instruction 2 0 None 1 Ambient temperature 2 External tuning temperature 3 CH1 heat exchanger inlet temperature 4 Notice for maintenance 5 Pressure of high pressure refrigerant circuit Data instruction 3 0 None 1 Ambient temperature 2 External tuning temperature 3 CH1 heat exchanger inlet temperature 4 Notice for maintenance 5 Pressure of high pressure refrigerant circ...

Page 53: ... Function 0x06 0 6 0x06 Address of the specified register 0x0043 0 0 4 3 0x00 0x43 Information written to 0043h Data instruction 0x0001 0 0 0 1 0x00 0x01 Checksum ASCII LRC RTU CRC B 5 0xB9 0xDE Trailer CR LF None Total quantity of byte 17 8 Response message 010600430001 Field name Example HEX ASCII mode character data RTU mode binary data Header None Slave Address 0x01 0 1 0x01 Function 0x06 0 6 ...

Page 54: ...ter 0x0038 0 0 3 8 0x00 0x38 Quantity of register to read 0x0001 0 0 0 1 0x00 0x01 Checksum ASCII LRC RTU CRC C 2 0xB0 0x07 Trailer CR LF None Total quantity of byte 17 8 Response 01040200FA Field name Example HEX ASCII mode character data RTU mode binary data Header None Slave Address 0x01 0 1 0x01 Function 0x04 0 4 0x04 Quantity of bytes to read 0x02 0 2 0x02 Information of 0038h Data display 1 ...

Page 55: ... when the customer device does not send messages regularly 4 1 Communication alarm occurs Fig 4 1 shows when an alarm occurs Refer to 4 3 for the setting method Communication alarm Operation continues when an alarm occurs Time for monitoring the communication alarm 180 sec When the customer s device is sending messages every 60sec if the communication cable is disconnected and no message is receiv...

Page 56: ...60 sec Broken wire o r coming off AL34 Communication alarm is generated Monitoring time Monitoring time Normal connection Communication alarm automatic restoration Write or read 60 sec Fig 4 2 Communication alarm restoration example 4 3 Setting method Set of serial communication is done from 1 4 Touch panel flow Refer to 2 Serial communication settings screen Indication Item Setting and selection ...

Page 57: ...asures for information security To ensure the security take measures that are applicable to the user s operating system With the network connection protect the system with a firewall No warranty is applied to any damage caused by network security issues such as unauthorized access One example of the information security is described below Discuss the network security measures with the network admi...

Page 58: ...d pair cable UTP with category 5 or more 10BASE T Shielded twisted pair cable STP or non shielded twisted pair cable UTP with category 3 or more Use straight cables for the twisted pair cable 5 3 Connected explanation Fig 5 1 Shows the connection with customer equipment Fig 5 1 Connection with the base One Point Connect Thermo chiller with the base device via a hub Cables connectors and hub shall ...

Page 59: ... 0 0 0 0 Port No 502 1 When default gateway is not used the value should be set to 0 0 0 0 5 5 Modbus TCP communication function Modbus protocol is a communication protocol developed by Modicon It is used to communicate with a PC or PLC Register content is read and written by this communication protocol This communication has the following features Controls run stop Sets and reads the circulating ...

Page 60: ...ct before sending the next message Retry resend request message The response may not be returned due to noise If no message is returned after sending a request message resend the request message If necessary send a read request message to check if it was written correctly When handling of the written request message is complete a positive message is returned Send a read request message to confirm ...

Page 61: ...IP Address IP Address 192 166 0 40 1 Current value of IP address 2 IP Address Setting IP Address Setting 3 Subnet mask Default gateway setting ubnet mask Default gateway setting 4 DIO Run Stop 2 RUN STOP by contact input 1 Disabled Enabled 1 Factory default status 2 RUN STOP operation is performed by contact input signal and Change of the circulating fluid temperature set value and Operation condi...

Page 62: ... method HRL Series 5 6 5 7 1 IP Address Setting Set window is open by pressing Change the IP address and press the button IP address will not change until the Thermo chiller is restarted After changing the IP address turn off the power supply and restart Thermo chiller ...

Page 63: ...lt gateway When the setting of the subnet mask and default gateway are changed the touch panel restarts Setting of the subnet mask and default gateway should be performed when the operation is stopped Change the setting of the subnet mask and default gateway only on the screen Otherwise Thermo chiller will not operate correctly ...

Page 64: ... corresponds with the remote Thermo chiller Refer to the document which is disclosed to the general users for details of the communication sequence 5 9 Message configuration Fig 5 9 1 shows the construction in which Request or Response are communicated in a capsule state on the Modbus TCP network Compared with the existing Modbus communication the function code and data are common A Transaction id...

Page 65: ... remote address but each device is identified by the IP address E Function Refer to 5 10 Function codes Designate command F Data Specify the register address quantity reading and writing in accordance with Function In Modbus TCP checksum CRC and LRC field are not available Data is checked by TCP IP and Ethernet processing data 5 10 Function codes Function codes for reading or writing the register ...

Page 66: ...rt function code and data part in 3 11 Explanation of function codes for serial communication Header Checksum and Trailer are not required for Modbus TCP communication In addition the slave address corresponds to the Unit identifier in Modbus TCP but this product identifies the fuselage by its IP address Please refer to 5 12 11 for a concrete communication example ...

Page 67: ...adecimal number 8000h to 7FFFh 0 1LPM dig 0037h CH2 Circulating fluid flow rate Decimal number 3276 8 to 3276 7LPM Hexadecimal number 8000h to 7FFFh 0 1LPM dig 0038h Data display 1 Follow the data instructions 1 0039h Data display 2 Follow the data instructions 1 003Ah Data display 3 Follow the data instructions 1 003Bh Data display 4 Follow the data instructions 1 003Ch Status flag Refer to 5 12 ...

Page 68: ...rogram No 10 decimal number 0 to 4294967295 16 hexadecimal number 00000000h to FFFFFFFFh 4 bytes 0063h upper level 0064h lower level 0064h 0065h Control board Program version 10 decimal number 0 to 65535 16 hexadecimal number 0000h to FFFFh 0066h Display Program No 10 decimal number 0 to 4294967295 16 hexadecimal number 00000000h to FFFFFFFFh 4 bytes 0063h upper level 0064h lower level 0067h 0068h...

Page 69: ...the same as serial communication Refer to 3 13 5 5 12 6 Alarm flag The communication content is the same as serial communication Refer to 3 13 6 5 12 7 Data display In the Ethernet mode the contents selected for Data instruction are displayed in Data display 1 to 4 The data types that can be displayed and their range are the same as for serial communication Refer to 3 13 7 5 12 8 Circulating fluid...

Page 70: ...et flag Alarm reset 0 None 1 Yes 3 to15 None Operation Start Command Ethernet mode you can control the operation start stop of this product However this function is invalidated when the setting of DIO Run Stop is ON on the touch panel Mode request flag The mode request flag can be switched to the Ethernet mode is changed from 0 to 1 After that even if it changes to 0 it keeps Ethernet mode For det...

Page 71: ...of serial communication 5 12 11 Product number Reads the product number of this product Communication example When reading the product number and serial number 〇 Unit identifier 1 Function code 04 Read 19 consecutive data from register 005h Product number HRL300 A 40 Serial number AA001 Required message010400500013 Field name Example HEX Binary data Unit identifier 0x01 0x01 Function 0x04 0x04 Fir...

Page 72: ...mber 11 12 0x3020 0x30 0x20 Information of 0056h Product number 13 14 0x2020 0x20 0x20 Information of 0057h Product number 15 16 0x2020 0x20 0x20 Information of 0058h Product number 17 18 0x2020 0x20 0x20 Information of 0059h Product number 19 20 0x2020 0x20 0x20 Information of 005Ah Product number 21 22 0x2020 0x20 0x20 Information of 005Bh Product number 23 24 0x2020 0x20 0x20 Information of 005...

Page 73: ...Refer to 5 12 11Communication example 5 12 13 Control board program number Reads the program number of the product 5 12 14 Control board program version Reads the program version of the product 5 12 15 Display program number Reads the display program number of the product 5 12 16 Display program version Reads the display program version of the product ...

Page 74: ...HRX OM Y120 Chapter 5 Ethernet Modbus TCP communication 5 12 Register Map HRL Series 5 18 ...

Page 75: ......

Page 76: ... Tel 81 3 5207 8249 Fax 81 3 5298 5362 URL https www smcworld com Note Specifications are subject to change without prior notice and any obligation on the part of the manufacturer 2022 SMC Corporation All Rights Reserved Revision Revision C Jul 2022 ...

Reviews: