Installation & Maintenance Manual
Fieldbus device (SI unit)
EX260 Series for PROFIBUS DP
EX260-TFN20
Installation
Safety Instructions
This manual contains essential information for the protection of users
and others from possible injury and/or equipment damage.
•Read this manual before using the product, to ensure correct handling,
and read the manuals of related apparatus before use.
•Keep this manual in a safe place for future reference.
•These instructions indicate the level of potential hazard with the labels
of "Caution", "Warning" or "Danger", followed by important safety
information which must be carefully followed.
•To ensure safety of personnel and equipment the safety instructions in
this manual and the product catalogue must be observed, along with
other relevant safety practices.
WARNING indicates a hazard with a medium level
of risk which, if not avoided, could result in death or
serious injury.
DANGER indicates a hazard with a high level of risk
which, if not avoided, will result in death or serious
injury.
CAUTION indicates a hazard with a low level of risk
which, if not avoided, could result in minor or
moderate injury.
Caution
Warning
Danger
Summary of Product element
Installation (Continued)
Installation (Continued)
This product is class A equipment that is intended for use in an industrial
environment.
There may be potential difficulties in ensuring electromagnetic
compatibility in other environments due to conducted as well as radiated
disturbances.
Setting
NOTE
When conformity to UL is necessary the SI unit must be used with a
UL 1310 Class2 power supply.
<EX260-SPR1/-SPR2/-SPR3/-SPR4>
5
1
7
2
6
4
6
4
3
5
7
8
8
<EX260-SPR5/-SPR6/-SPR7/-SPR8>
Fieldbus interface
connector (BUS OUT)
Element
Description
PROFIBUS DP connection
(M12 5-pole socket, B-coded)
Fieldbus interface
connector (BUS IN)
PROFIBUS DP connection
(M12 5-pole plug, B-coded)
Fieldbus interface
connector
PROFIBUS DP connection
(D-sub 9-pole socket)
Ground terminal
Functional earth (M3 screw)
Output connector
Output signal interface for valve manifold
1
No.
2
3
5
6
2 pcs. M3x30 screw for connection to the valve
manifold
Seal cap
※
1 pc. seal cap for unused fieldbus interface
connector (BUS OUT)
Accessories
LED and switch
Bus status−specific and SI unit−specific LEDs
Switches for setting of node address and
operating mode
Mounting hole
Mounting hole for connection to the valve manifold
7
8
Power supply
connector
Power supply with load voltage for valves and
operating voltage for SI unit
(M12 5-pole plug, A-coded)
4
Hexagon socket head cap
screw
Note: Seal cap will be required only for EX260-SPR1/-SPR2/-SPR3/-SPR4.
General instructions on installation and maintenance
Connect valve manifold to the SI unit.
Connectable valve manifolds are the same as for EX250 series SI unit.
Refer to the EX250 series valve manifold section in the valve catalogue
for valve manifold dimensions.
M3 hexagon screw
Tightening torque 0.6 Nm
Valve manifold
∗
: Thread size: M3×30
Replacement of the SI unit
•Remove the M3 hexagon screws from the SI unit and release the SI unit
from the valve manifold.
•Replace the SI unit.
•Tighten the screws with the specified tightening torque. (0.6 Nm)
Precautions for maintenance
•Be sure to switch off the power.
•Check there is no foreign matter inside the SI unit.
•Check there is no damage and no foreign matter being stuck to the
gasket.
•Be sure to tighten the screws with the specified torque.
If the SI unit is not assembled properly, inside PCBs may be damaged or
liquid and/or dust may enter into the unit.
Assembly and disassembly of the SI unit
Connecting cables
Select the appropriate cables to mate with the connectors mounted on the
SI unit.
Fieldbus interface connector layout
<EX260-SPR1/-SPR2/-SPR3/-SPR4>
BUS OUT: M12 5-pole socket B-coded
1
5
3
4
2
2
5
4
3
1
Power supply connector layout
1
4
5
2
3
PWR: M12 5-pole plug A-coded
Ground terminal
Connect the ground terminal to ground.
Resistance to ground should be 100 ohms or less.
-
Designation
Description
Unused
RXD/TXD-N
Receive/transmit data, negative
-
Unused
-
Unused
1
No.
2
3
5
RXD/TXD-P
Receive/transmit data, positive
4
SV24 V
Designation
Description
+24 V for solenoid valve
SV0 V
0 V for solenoid valve
SI24 V
+24 V for SI unit operation
-
Unused
1
No.
2
3
5
SI0 V
0 V for SI unit operation
4
BUS IN: M12 5-pole plug B-coded
-
Designation
Description
Unused
RXD/TXD-N
Receive/transmit data, negative
-
Unused
-
Unused
1
No.
2
3
5
RXD/TXD-P
Receive/transmit data, positive
4
BUS: D-sub 9-pole socket
-
Designation
Description
Unused
-
Unused
RXD/TXD-P
Receive/transmit
data, positive
DGND
Data ground (reference
potential to VP)
1
No.
2
3
5
-
Unused
4
VP
Power supply plus
(P5V)
-
Unused
-
Unused
6
7
9
RXD/TXD-N
Receive/transmit
data, negative
8
<EX260-SPR5/-SPR6/-SPR7/-SPR8>
1
2
3
4
5
6
7
8
9
Threaded screw
hole size: #4-40
PROFIBUS DP address setting and Fail safe setting (SETTINGS)
<PROFIBUS DP address setting (ADDRESS)>
The PROFIBUS DP address is binary coded and can be set from 1 to
125 using the 8-element switch.
Note: Factory default setting is Address 1.
<Fail safe setting (OUTPUT STATE)>
Set the reaction of outputs to the communication error.
CLEAR: Clear all outputs.
HOLD: Hold the last state before communication error.
Note: Factory default setting is CLEAR.
Note: Be sure to switch off the power supply before setting the switches.
2 3 4 5 6 7 8
ON 1
Switch No
No.2
No.1
No.4
No.3
No.6
No.5
No.8
No.7
ADDRESS
64
-
16
32
4
8
1
2
1
0
0
0
0
0
1
0
2
0
0
0
0
0
0
1
3
0
0
0
0
0
1
1
4
0
0
0
1
0
0
0
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
125
1
1
1
1
1
1
0
OUTPUT
STATE
-
0
HOLD
-
1
0: OFF, 1: ON
CLEAR
•Do not disassemble, modify (including changing the printed circuit
board) or repair.
An injury or failure can result.
•Do not operate the product outside of the specifications.
Do not use for flammable or harmful fluids.
Fire, malfunction, or damage to the product can result.
Verify the specifications before use.
•Do not operate in an atmosphere containing flammable or
explosive gases.
Fire or an explosion can result.
This product is not designed to be explosion proof.
•If using the product in an interlocking circuit:
•
Provide a double interlocking system, for example a mechanical
system.
•
Check the product regularly for proper operation.
Otherwise malfunction can result, causing an accident.
•The following instructions must be followed during maintenance:
•
Turn off the power supply.
•
Stop the air supply, exhaust the residual pressure and verify that the
air is released before performing maintenance.
Otherwise an injury can result.
•After maintenance is complete, perform appropriate functional
inspections.
Stop operation if the equipment does not function properly.
Safety cannot be assured in the case of unexpected malfunction.
•Provide grounding to assure the safety and noise resistance of the
Fieldbus system.
Individual grounding should be provided close to the product with a
short cable.
Warning
Caution