Wiring

Wiring of power supply

The Power supply connection inside the unit has individual power
supplies for solenoid valve actuation (SV power supply) and for Sensor
(SW power supply). Supply 24V DC for each of them.

Either single or dual power supply is available. Wiring is not necessary
for SW power supply when no Input Blocks are used.

*In case of single power supply, pay attention to the range of each
supply voltage.

Names and Functions of Individual Parts (continue)

PWR(V) PWR

MOD/NET

SETTINGS

1

0

PWR(V):
Power LED for
output equipment

PWR:
Power LED for SI unit
and Input block

MOD/NET

Indication

Contents

PWR (V)

Light ON when power for solenoid valve is supplied.

PWR

Light ON when power for DeviceNet line is supplied.

MOD /

NET

Light OFF Power off,off line or Duplicate MAC ID.

Green
flashing

Waiting for connection (ON line)

Green
Light ON

Connection completed (ON line)

Red
flashing

Connection timed out (Minor communication
error)

Red
Light ON

MAC ID duplication error or BUS OFF error
(Major communication error)

Voltage reduction of approx.1V

24V DC

SI unit

Input Block

23V DC

Sensor

Power for a sensor is supplied to the sensor connected to an Input Block.
There will be a voltage drop of up to approx. 1V inside the SI unit,
therefore select a sensor which will operate with the resultant voltage.

If a sensor requires 24V, it is necessary to lower power supply voltage
for sensor slightly or secure a power supply for sensor separately without
going through the SI unit so that sensor input voltage can be 24V with
actual loading (allowable voltage of sensor power supply : 19.2V to
28.8V).

Power supply connector

M12 5pin (Plug)

Communication connector

M12 5pin (Plug) [Special for DeviceNet]

3

2

1

4

5

3

2

1

4

5

No.

Description

Function

1

SV 24V

For solenoid valve +24V

2

SV 0V

For solenoid valve 0V

3

SW 24V

For sensor unit +24V

4

SW 0V

For sensor unit 0V

5

E

Earth

No.

Description

Function

1

Drain

Drain / Shield

2

V +

Power  for circuit

3

V -

Power supply - for circuit

4

CAN_H

Signal wire H

5

CAN_L

Signal wire L

SW Setting

Address setting

When DIP switch is to be set, turn OFF power supply to SI unit.

Position of DIP switch

DIP switch

M3 pan head screw
Tightening torque : 0.6N . m

SW1

1.Default value of address and baud rate.

Node address and baud rate are preset to 63, 125kbps respectively at
the shipment in either HW mode or SW mode.

2.In SW mode, setting value of address and baud rate are retained even

after power supply is off.

3.In HW mode, once power supply is turned off and turned on again,

then setting value of address and baud rate in S/W mode are erased.
Address and baud rate can be set again by setting switch SW1.

Example

4.Output with communication stopped is set to 0 (full output clear mode)

at shipment from factory. It is possible to change setting of single
output when communication stopped. In this case,setting of SW1-9
becomes invalid.

SW mode

Address : 63
Baud rate : 125kbps

HW mode

Address : 0
Baud rate : 500kbps

SW mode

Address : 0
Baud rate : 500kbps

LED indication

0

Set address and Baud rate
by SW1 to 8

Set address and Baud rate
by network.
SW1 to 8 are invalid.

HW mode

1

SW mode

Mode setting

Setting of solenoid output state in communication fault
  Solenoid output state:Communication stops (I/O connection time out)
 

or fault message is received. 

Solenoid output state

All solenoid valve outputs are held before communication fault.
(Fault state=1 , Fault value=0)
All solenoid outputs are reset to zero.
(Fault state=0 , Fault value=0)

HOLD

CLEAR

SW9

1

0

Setting of address

Address

#0

#1

#2

#62

#63

SW1

1

0

1

0

0

1

SW2

2

0

0

1

1

1

SW3

4

0

0

0

1

1

SW4

8

0

0

0

1

1

SW5

16

0

0

0

1

1

SW6

32

0

0

0

1

1

Setting of Baud rate

SW7 SW8

Baud rate

(kbps)

0

1

0

1

0

0

1

1

Setting

125

250

500

Not used

..

.

1

2

3

4

5

6

7

8

9 10

ON

1

0

Error Display Function

MOD/NET LED

Cause & Countermeasure

Light OFF

PWR LED Light OFF
<Countermeasure>
Confirm that power for SI unit circuit is supplied.
Confirm correct wiring for circuit.
If above countermeasures do not improve status, please
exchange SI unit.

PWR LED Light ON
<Countermeasure>
Confirm that baud rate is set correctly.
If MOD/NET LED light is OFF in spite of baud rate is set
correctly, exchange SI unit.

Green flashing

Connection waiting
Shows communication waiting status between SI unit and
master.
<Countermeasure>
Confirm master is operating correctly.
If using scan list, ensure slave is recorded to scan list
correctly.

Red flashing

Communication wire disconnected error
Warning for SV supply voltage drop
(Except for EX250-SDN1-X102)
<Countermeasure>
Confirm communication wire is connected.
Confirm SV power supply voltage is according to
specification. (21.6 to 26.4V)
(Except for EX250-SDN1-X102)
<Remark>
Red flashing if master power source is turned off during
communication.

Red Light ON

Node address overlapping error
<Countermeasure>
Confirm there is no overlapping on the node address.

BUS OFF error
Detects communication error.
<Countermeasure>
Case 1
Communication error due to noise.
Confirm there is no component or high voltage cable that
generates noise around communication wire.
Make some distances between communication wire and
noise source.
Case2
Communication cable problem
Confirm terminal resistance (121ohm) is connected to
both ends of DeviceNet communication wire.

If red MOD/NET LED is still ON despite above
countermeasures, exchange SI unit.

When red MOD/NET LED is ON, even if cause is solved, the SI unit
does not perform auto-recovery. In this case, please reset the power
to SI unit circuit (Communication/Internal power supply).

Error Display Function (continue)

EX250-TFI73GB-A

AUSTRIA

(43) 2262 62280

NETHERLANDS

(31) 20 531 8888

BELGIUM

(32) 3 355 1464

NORWAY

(47) 67 12 90 20

CZECH REP.

(420) 541 424 611

POLAND

(48) 22 211 9600

DENMARK

(45) 7025 2900

PORTUGAL

(351) 21 471 1880

FINLAND

(358) 207 513513

SLOVAKIA

(421) 2 444 56725

FRANCE

(33) 1 6476 1000

SLOVENIA

(386) 73 885 412

GERMANY

(49) 6103 4020

SPAIN

(34) 945 184 100

GREECE

(30) 210 271 7265

SWEDEN

(46) 8 603 1200

HUNGARY

(36) 23 511 390

SWITZERLAND

(41) 52 396 3131

IRELAND

(353) 1 403 9000

UNITED KINGDOM

(44) 1908 563888

ITALY

(39) 02 92711

URL http://www.smcworld.com (Global) http://www.smceu.com (Europe)

Specifications are subject to change without prior notice from the manufacturer.
© SMC Corporation All Rights Reserved.

Contact

Reviews: