background image

No.EX##-OMO0004-A 

 

 

 

 

 

 

 

 

PRODUCT NAME 

 

SI unit

 

for DeviceNet

TM

 

 

MODEL / Series / Product Number 

 

EX180-SDN3/4/5/6

 Series

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

Summary of Contents for EX180 Series

Page 1: ...No EX OMO0004 A PRODUCT NAME SI unit for DeviceNetTM MODEL Series Product Number EX180 SDN3 4 5 6 Series ...

Page 2: ...mary of Product Parts 8 Installation and Cabling 9 General Instructions on Installation 9 Connecting Cables 10 LED Display and Settings 12 DeviceNetTM Objects 15 Troubleshooting and Maintenance 24 Maintenance 29 Specifications 30 Table of Specifications 30 Dimensions 32 ...

Page 3: ... of equipment failure when configuring the equipment 2 Only personnel with appropriate training should operate machinery and equipment The product specified here may become unsafe if handled incorrectly The assembly operation and maintenance of machines or equipment including our products must be performed by an operator who is appropriately trained and experienced 3 Do not service or attempt to r...

Page 4: ...placement product or necessary parts will be provided This limited warranty applies only to our product independently and not to any other damage incurred due to the failure of the product 3 Prior to using SMC products please read and understand the warranty terms and disclaimers noted in the specified catalog for the particular products 2 Vacuum pads are excluded from this 1 year warranty A vacuu...

Page 5: ...in an atmosphere containing flammable or explosive gases Fire or an explosion can result This product is not designed to be explosion proof If using the product in an interlocking circuit Provide a double interlocking system for example a mechanical system Check the product regularly for proper operation Otherwise malfunction can result causing an accident The following instructions must be follow...

Page 6: ...is exceeded the mounting screws may be broken Never mount a product in a location that will be used as a foothold The product may be damaged if excessive force is applied by stepping or climbing onto it Wiring Avoid repeatedly bending or stretching the cables or placing heavy load on them Repetitive bending stress or tensile stress can cause breakage of the cable Wire correctly Incorrect wiring ca...

Page 7: ...to sunlight shade the product from the sunlight Otherwise failure or malfunction can result Keep within the specified ambient temperature range Otherwise malfunction can result Do not operate close to a heat source or in a location exposed to radiant heat Otherwise malfunction can result Adjustment and Operation Set the switches by using a sharp pointed screwdriver etc It may damage set switches P...

Page 8: ... 7 No EX OMO0004 A How to Order EX180 series SI unit Accessories Communication connector Accessories Power supply connector ...

Page 9: ...s No Element Description 1 Fieldbus interface connector BUS The connector for DeviceNetTM that is used to connect to the DeviceNet TM bus line 2 Socket for the power supply PWR V The connector for the power supply that is used to supply the power for the solenoid valves 3 FG terminal Functional Earth 4 Display LED diagnostic display 5 Switch setting part Configures the MAC ID communication speed ...

Page 10: ...ogues and operation manuals for details on the solenoid valves and manifolds How to mount the manifold 1 Mount the SI unit to the manifold so that the mounting guide of the SI unit case mates with the manifold groove 2 Secure the SI unit using the two sliding locks Caution The EX180 SDN1 2 can not mount on the valve manifold for the EX180 SDN3 4 5 6 The EX180 SDN3 4 5 6 also can not mount on the v...

Page 11: ...ned pins Figure 1 The DeviceNetTM communication connector is suitable for use with wire sizes from AWG24 to 12 0 2 mm2 to 2 5 mm2 The required tightening torque is 0 5 to 0 6 Nm Figure 1 2 A bus termination is required at both ends of DeviceNetTM bus segment as shown in the Figure 2 The specification of the terminating resistor is 121 Ω 1 1 4 W Figure 2 3 How to connect Figure 3 ...

Page 12: ... from AWG28 to 16 0 14 mm2 to 1 5 mm2 The EX180 power supply structure consists of two systems These systems can operate alone or with another power supply Wire to the assigned pins Figure 4 Figure 5 The tightening torque is 0 22 to 0 25 Nm Note Ground the FG terminal with a ground resistance of 100 Ω or less A Dual power supplies B Single power supply Figure 4 Figure 5 ...

Page 13: ...ly for DeviceNet TM is supplied ON PWR Communication power supply for DeviceNet TM is not supplied OFF Communication power supply for DeviceNet TM is OFF off line or a MAC ID duplication is present OFF I O connection is waiting On line status Green flashing I O connection is established On line status Green ON I O connection time out Minor communication error Red flashing MNS MAC ID duplication er...

Page 14: ... 13 No EX OMO0004 A Switch setting Turn off the power supply while setting the DIP switches Open the cover and set the DIP switches with a small flat blade screwdriver ...

Page 15: ...hown in the Figure a If you mount a single solenoid valve on the standard wiring manifold output number for B side valve is skipped Custom wiring for mixed mounting single solenoid valves and double solenoid valves can be specified with a Wiring Specification Sheet Example wiring is shown in the Figure b Bit status 0 and 1 on a data corresponds solenoid valve status ON and OFF 0 OFF 1 ON and outpu...

Page 16: ...pecific 1 Identity Object Class ID 01h 1 1 Class attribute ID Access rule Description Value 1 2 Class common service Service code Service name 1 3 Instance attribute ID Access rule Description Value 1 Get Vender ID 07h 2 Get Device Type 1Bh 3 Get Product Code 87h 135 EX180 SDN3 SDN3A 88h 136 EX180 SDN4 SDN4A 89h 137 EX180 SDN5 SDN5A 8Ah 138 EX180 SDN6 SDN6A 4 Get Revision Per unit 5 Get Status 6 G...

Page 17: ... ID 03h 3 1 Class attribute ID Access rule Description Value 1 Get revision 2 3 2 Class common service Service code Service name 0Eh Get_Attribute_Single 3 3 Instance attribute ID Access rule Description Value 1 Get Set 1 MAC ID 0 63 2 Get Set 1 Baud Rate 0 2 3 Get Set BOI 0 1 4 Get Set Bus off Counter 0 255 5 Get Allocation Information 6 Get MAC ID Switch Changed 0 1 7 Get Baud Rate Switch Change...

Page 18: ...ervice name 4 3 Instance attribute ID Access rule Description 3 Get Set Data 4 4 Solenoid Output Assembly Instance Instance Type Description Byte 35 Output 16 Solenoid Output Points 02h 37 Output 32 Solenoid Output Points 04h The data format is shown below Data ID Byte offset bit7 bit0 0 OUT7 OUT6 OUT5 OUT4 OUT3 OUT2 OUT1 OUT0 35 1 OUT15 OUT14 OUT13 OUT12 OUT11 OUT10 OUT9 OUT8 0 OUT7 OUT6 OUT5 OUT...

Page 19: ...e Description Value 1 Get State 2 Get Instance_type 00h 3 Get TransportClass_trigger 83h 4 Get DeviceNet TM _produced_connection_id 5 Get DeviceNet TM _consumed_connection_id 6 Get DeviceNet TM _initial_comm_characteristics 21h 7 Get Produced_connection_size FFFFh 8 Get Consumed_connection_size FFFFh 9 Get Set Expected_packet_rate 12 Get Set Watchdog_timeout_action 13 Get Produced_connection_path_...

Page 20: ...cs 01h 7 Get Produced_connection_size 00h 8 Get Consumed_connection_size 04h EX180 SDN3 EX180 SDN3A 04h EX180 SDN5 EX180 SDN5A 02h EX180 SDN4 EX180 SDN4A 02h EX180 SDN6 EX180 SDN6A 9 Get Set Expected_packet_rate 12 Get Set Watchdog_timeout_action 13 Get Produced_connection_path_length 0 14 Get Produced_connection_path None 15 Get Consumed_connection_path_length 6 16 Get Consumed_connection_path 20...

Page 21: ...te 8 Get Consumed_connection_size 0 Byte 9 Get Set Expected_packet_rate 12 Get Set Watchdog_timeout_action 13 Get Produced_connection_path_length 0 14 Get Produced_connection_path None 15 Get Consumed_connection_path_length 4 Ack present 0 Ack not present 16 Get Consumed_connection_path 20h 2Bh 24h 01h Ack present None Ack not present 17 Set Production_inhibit_time 5 6 Instance common service Serv...

Page 22: ...Service name 0Eh Get_Attribute_Single 10h Set_Attribute_Single 6 5 Specific service None 7 Parameter Object Class ID 0Fh 7 1 Class attribute ID Access rule Description Value 2 Get Max Instance 4 8 Get Parameter Class Descriptor 1 9 Get Configuration Assembly Instance 0 7 2 Class common service Service code Service name 0Eh Get_Attribute_Single 7 3 Instance attribute 1 SOLV Status ID Access rule De...

Page 23: ...ue 0 DIP SW valid 1 EEPROM valid 2 Get Link Path Size 6 3 Get Link Path 20h 64h 24h 01h 30h 68h 4 Get Descriptor 20h 5 Get Data Type C1h 6 Get Data Size 1 7 6 Instance attribute 4 Hold Clear Select Connection Delete ID Access rule Description Value 1 Get Parameter Value 0 Fault action is valid 1 Clear is valod 2 Set Link Path Size 6 Link Path 20h 64h 24h 01h 30h 69h Segment type port 3 Set Segment...

Page 24: ...9 2 Class common service Service code Service name 9 3 Instance attribute ID Access rule Description Value 100 Get SOLV Status 0 OK 1 Abnormal valve power supply voltage 101 Get SOLV Fuse Status 0 OK 1 Valve power supply fuse has blown 104 Get Set Hold Clear Time Out 0 DIP switch is valid Initial value 1 EEPROM valid 105 Get Set Hold Clear Connection Delete Setting 0 Fault action is valid Initial ...

Page 25: ...lfunctioning of the SI unit is caused by the operating environment network structure Please consult SMC if further troubleshooting is necessary Yes No The solenoid valve does not work correctly Solenoid valve failure Only LED of the solenoid valve is ON Refer to reference No 2 SI unit works properly PWR LED is OFF PWR V LED is OFF MNS LED is OFF MNS LED flashes green Solenoid valve malfunction Ref...

Page 26: ...onfirm the DeviceNet TM supply voltage for communication is within specifcaiton Supply 11 to 25 VDC to the communication power supply for DeviceNetTM Check the cable for the solenoid valve is not broken and confirm that the connection between the power supply cable and the connector is not loose Confirm that repeated bending stress or pulling force which can cause a broken wire is not applied to t...

Page 27: ...tion speed setting of the SI unit and the communication speed setting of the master and slave station are the same Set the communication speed correctly MAC ID duplication Check that there is no MAC ID duplication between the master and slaves Set MAC ID correctly Check the wiring length of the communication line and the presence of the termination resistors at both ends of the DeviceNetTM network...

Page 28: ... Confirm that repeated bending stress or pulling forces which can cause a broken wire is not applied to the cable Connect DeviceNetTM cable correctly Confirm that the communication speed setting of the SI unit and the communication speed setting of the master and slave station are the same Set the communication speed correctly 5 MNS LED flashes red I O connection time out Confirm that power is sup...

Page 29: ...d Connect the SI unit and valve manifold properly The solenoid valve does not work Check the total number solenoid valves connected to the manifold does not exceed the max number of outputs of the SI unit The number of solenoid valve outputs that can be connected to the manifold has to be smaller or equal to the max number of outputs EX180 SDN3 EX180 SDN5 Max 32 outputs EX180 SDN4 EX180 SDN6 Max 1...

Page 30: ... No problem is found on the appearance or the conductor resistance value Confirm that the resistance value does not exceed the specification If any visible problem is found or the conductor resistance value is out of specification replace the cable SI unit No abnormal operation or LED display Replace the SI unit if the operation or LED display is abnormal Power supply Item Criterion Remedy Measure...

Page 31: ...d surge voltage suppressor of 24 VDC and 1 W or less manufactured by SMC Output specification Output setting at the time of communication error Hold Clear Switch setting Enclosure IP20 Withstand voltage 500 VAC 1 min Between FG and external terminal Insulation resistance 10 MΩ or more 500 VDC Between FG and external terminal Ambient temperature Working temperature 10 to 50 o C Storage 20 to 60 o C...

Page 32: ...N6 Vender ID 7 SMC Corp Applicable message Duplicate MAC ID Check Message Unconnected Explicit Message Explicit Message MAC ID set range 0 to 63 Data rate 125 kbps 250 kbps 500 kbps Thick cable 500 m or less 250 m or less 100 m or less Max length of the network Thin cable 100 m or less 156 m or less 78 m or less 39 m or less Total main and branch line length Max length of branch line is 6 m Occupi...

Page 33: ... 32 No EX OMO0004 A Dimensions Unit mm EX180 SDN3 4 5 6 EX180 SDN3A 4A 5A 6A ...

Page 34: ...istory A Revision page 2 page 31 Note Specifications are subject to change without prior notice and any obligation on the part of the manufacturer DeviceNet TM is a trademark of ODVA 2010 2011 SMC Corporation All Rights Reserved ...