ClimateWorx ProtoNode Start-up Guide
Page 18 of 46
4.5 Power-Up ProtoNode
Check power requirements in the table below:
Power Requirement for ProtoNode External Gateway
Current Draw Type
ProtoNode Family
12V DC/AC
24V DC/AC
30V DC
FPC
– N34 (Typical)
170mA
100mA
80mA
FPC
– N34 (Maximum)
240mA
140mA
100mA
FPC
– N35 (Typical)
210mA
130mA
90mA
FPC
– N35 (Maximum)
250mA
170mA
110mA
NOTE:
These values are ‘nominal’ and a safety margin should be added to the power supply of the host
system. A safety margin of 25% is recommended.
Figure 16: Required current draw for the ProtoNode
Apply power to ProtoNode as show below in
. Ensure that the power supply used
complies with the specifications provided in
ProtoNode accepts either 9-30V DC or 12-24V AC on pins 4 and 5.
Frame GND should be connected.
Power to
ProtoNode
ProtoNode
Pin #
Pin
Assignment
Power In (+)
Pin 4
V +
Power In (-)
Pin 5
V -
Frame Ground
Pin 6
FRAME GND
Figure 17: Power Connections