ClimateWorx ProtoNode Start-up Guide
Page 10 of 46
3.4 Selecting the Desired Field Protocol
ProtoNode FPC-
N34 units use the “S” bank of DIP switches (S0 – S3) to select the Field
Protocol.
o
See the table in
for the switch settings to select
o
The OFF position is when the DIP switches are set closest to the outside of the box
ProtoNode FPC-
N35 units do not use the “S” bank DIP switches (S0 – S3) to select a Field
Protocol.
o
On ProtoNode FPC-N35 units, these switches are disabled; the Field Protocol is always
LonWorks
ProtoNode FPC-N34
S Bank DIP Switches
Profile
S0
S1
S2
S3
BACnet/IP
Off
Off
Off
Off
BACnet MS/TP
On
Off
Off
Off
Metasys N2
Off
On
Off
Off
Modbus TCP/IP
On
On
Off
Off
BACnet Ethernet
Off
Off
On
Off
NOTE:
When setting DIP Switches, ensure that power to the board is OFF.
S0
– S3 DIP
Switches
S Bank DIP Switch Location
Profile Settings for ProtoNode
Figure 5: S Bank DIP Switches
S0
S1
S2
S3
Off
On