ELECTRICAL WIRING

!

Without Output Function (IP8001-030, IP8001-033)

(1) Remove the positioner body cover.

(2) Connect  the  input  current  wiring  from  an  adjusting  meter  (controller)

following Fig. 7.

!

With Output Function (IP8001-032)

(1) Remove the positioner body cover.

(2) Connect  input  current  wiring  from  an  adjusting  meter  (controller)  and

each output wiring following Fig. 8.

8

DESCRIPTION OF COMPONENTS

9

MAINTENANCE

WARNING:

!

Do  not  dis-assemble  the  product.  A  product  which  has  been  dis-
assembled cannot be guaranteed. Consult with SMC if dis-assembly is
necessary.

!

After installation, repair and dis-assembly, connect compressed air and
perform a proper functional test and leak test. If bleed noise is louder
than the initial state or operation is abnormal, stop operation and check
if installation is correct or not. 

CAUTION:

!

Check  if  supply  air  is  clean.  Inspect  compressed  air  cleaning  system
periodically so that dust, oil and humidity, which can cause malfunction
and failure of the unit, do not enter the equipment.

!

If handled improperly, compressed air can be dangerous. Maintenance
and replacement of unit parts should only be performed by trained and
experienced  personnel  for  instrumentation  equipment,  as  well  as
following the product specifications.

9

MAINTENANCE (CONTINUED)

!

Check  the  positioner  once  a  year.  If  excessively  worn  diaphragms, 
O-rings  or  seals  are  found,  or  any  unit  that  has  been  damaged, 
replace  with  new  units.  Treatment  at  an  early  stage  is  especially
important if the positioner is used in a place of severe environment like
coastal area.

!

Before removing the positioner for maintenance or replacing unit parts
after  installation,  make  sure  the  supply  pressure  is  shut  off  and  all
residual air pressure is released from piping.

!

When  the  fixed  orifice  is  clogged  with  carbon  particles  or  others,
remove  the  pilot  valve  unit  Auto/Manual  switch  screw  (built-in  fixed
orifice) and clean it by inserting a f0.2 wire into the aperture. If it must
be replaced with a new one, stop the supply pressure and remove the
stopper screw of the pilot valve unit.

!

When disassembling the pilot valve, coat grease on the O-ring of the
sliding section. (Use TORAY SILICONE SH45 grease)

!

Check  for  air  leaks  from  the  compressed  air  piping.  Air  leaks  could
lower the performance characteristics of the positioner. Air is normally
discharged  from  a  bleed  port,  but  this  is  necessary  air  consumption
based on the construction of the positioner, and is not an abnormality
if the air consumption is within the specified range.

!

When  replacing  piping  to  change  the  operating  direction,  be  sure  to
perform span adjustment (parameter code: C70).

!

When removing the positioner from the actuator and mounting it onto
another  actuator,  malfunctions  may  occur  due  to  its  retained  initial
constant. Therefore, when it is mounted onto other actuators, transmit
the  input  current  while  cutting  the  air  supply,  and  shift  to  parameter
mode for adjustments.

!

The  balance  current  will  change  depending  on  the  positioner
orientation.  Adjust  the  balance  current  (parameter  code:  C60)  every
time the orientation changes.

10 LIMITATIONS OF USE

WARNING:

!

Do  not  exceed  any  of  the  specifications  laid  out  in  section  2  of  this
document or the specific product catalogue.

!

Read  thoroughly  and  understand  the  operation  manual  before
operation of this product.

11 CONTACT LIST

SMC Corporation

Country

Telephone

Country

Telephone

Austria

(43) 2262 62280

Netherlands

(31) 20 531 8888

Belgium

(32) 3 355 1464 

Norway

(47) 67 12 90 20

Czech Republic

(420) 541 424 611 

Poland

(48) 22 211 9600 

Denmark

(45) 7025 2900 

Portugal

(351) 21 471 1880 

Finland

(358) 207 513513 

Slovakia

(421) 2 444 56725

France

(33) 1 6476 1000 

Slovenia

(386) 73 885 412

Germany

(49) 6103 4020 

Spain

(34) 945 184 100 

Greece

(30) 210 271 7265 

Sweden

(46) 8 603 1200 

Hungary

(36) 23 511 390 

Switzerland

(41) 52 396 3131 

Ireland

(353) 1 403 9000 

United Kingdom

(44) 1908 563888 

Italy

(39) 02 92711

Websites

SMC Corporation

www.smcworld.com

SMC Europe

www.smceu.com

Fig. 9






4 to 20mADC 

input current terminal 

1

2

3

4
5

6
7

8

4 to 20mADC 

input current terminal 

4 to 20mADC 

analog output terminal 

Alarm output 1 terminal 

Alarm output 2 terminal 

1

2

3

4
5

6
78

Fig. 7

Fig. 8

CHRYSSAFIDIS S.A./ ATHENS: 3 AGRINIOU STR, TAVROS - (+30) 210 4836315-20 / THESSALONIKI: DA12A STR, OT32, BIPE SINDOU - (+30) 2310 754681-4 / www.chryssafidis.com / [email protected] 

Reviews: