Version 6.00 
Date of editing: 16.09.2022 r. 

Page 9 z 18 

Installation manual 

KWP-O-ES

 

SMAY offers four basic types of damper battery systems.  

 

Arrangement 1

 

 vertical battery consisting of two fire dampers KWP (Figure 11) 

 

a.

 

Fix the gasket on insulating spacer of one of adjoining fire dampers (position (1) in the Figure 11).  

b.

 

Put non-combustible mineral wool into recess in upper surface of the fire damper. The thickness of mineral wool 

should be twice as the thickness of the recess in upper surface of the fire damper in order to fill the whole free 

space between the fire dampers as shown in (w1). 
 
NOTE: The alternative way of wool mounting is to use two layers of wool with thickness of 30 mm. In this case, 

apply  the  fire  resistant  PROMASTOP-Coating  with  width  of  50  mm.  The  mass  is  placed  between  the  strips  of 

wool and between wool and damper housings. 
 

c.

 

Place  the fire  damper  A on  the  fire damper  B  and  assemble  them  together on  the  front  and  back  with  use  of 

perforated assembly strips (2) and self-tapping screws M6x16 (3), which should be tightened into the openings 

in fire damper body. In order to carry out the correct assembly, 4 self-tapping screws should be used per each 

assembly strip with length of 1200 [mm].  
 

 

 

 

Figure 9. Arrangement 1 - vertical battery consisting of two fire dampers KWP

 

 

Summary of Contents for KWP-O-E

Page 1: ...a Installation manual KWP O E S Fire Damper rectangular v https www smay eu ...

Page 2: ...ght to make changes to this document TABLE OF CONTENT INSTALLATION TECHNOLOGY 2 I INSTALLATION TECHNOLOGY RIGID WALL 3 II INSTALLATION TECHNOLOGY FLEXIBLE WALL 5 III INSTALLATION TECHNOLOGY CEILING 6 IV INSTALLATION TECHNOLOGY STRUCTURES THICKER THAN 135 MM 8 V INSTALLATION TECHNOLOGY FOR FIRE DAMPERS IN BATTERIES 8 ...

Page 3: ...tion elements must be compatible with standard 1366 2 Minimal 200 mm between fire damper which are installed in different ventilating wires Minimal 75 mm between fire damper and construction element wall ceiling Before installing fire dampers please read assembly technology recommended by the manufacturer The way of installing recommended by one manufacturer may not be the same for other dampers R...

Page 4: ...er body dimension 60 mm from one side fix it with suspension Z1 and from other side fix it to the ventilation duct suspended on Z2 suspension c After setting the fire damper as described fill the gap between the fire damper and the wall with cement cement lime mortar concrete or PROMASTOP MG III made by PROMAT d After 48 hours from the installation the suspensions and supports used during installa...

Page 5: ...Version 6 00 Date of editing 16 09 2022 r Page 4 z 18 Installation manual KWP O ES Figure 3 Installation method of fire dampers KWP O in rigid wall ...

Page 6: ...al Firesilicone B1 FR c Put the closed fire damper into the installation opening and support or suspend in this way that the minimum installation depth mark is on the plane of the flange surface d After setting the fire damper as described fill the gap between the fire damper and the wall with non flammable mineral wool of high density 80 kg m3 or more e Seal the place of filling with mineral wool...

Page 7: ...een the fire damper and the wall with cement cement lime mortar concrete Under difficult working conditions producer recommend PROMASTOP MG III mortar of production of the PROMAT company d Mount the mounting brackets on each side Number of mounting brackets Side length up to 500 mm 1 pcs Side length from 500 to 800 mm 2 pcs e Housing install with actuator similarly as in the picture Only the lengt...

Page 8: ...Version 6 00 Date of editing 16 09 2022 r Page 7 z 18 Installation manual KWP O ES Figure 6 Installation method of fire dampers KWP O in ceiling ...

Page 9: ...y There are two possibilities of realizing the order of fire damper batteries basic and complete First one covers the set of fire dampers assembly strips and complete set of self tapping screws The purchase of other materials needed such as intumescent gasket PROMASEAL PL PVC SK mineral wool for thermal insulation with minimum density of 60 kg m3 and aluminum tape remains with the Customer The sec...

Page 10: ...ree space between the fire dampers as shown in w1 NOTE The alternative way of wool mounting is to use two layers of wool with thickness of 30 mm In this case apply the fire resistant PROMASTOP Coating with width of 50 mm The mass is placed between the strips of wool and between wool and damper housings c Place the fire damper A on the fire damper B and assemble them together on the front and back ...

Page 11: ...e way of wool mounting is to use two layers of wool with thickness of 30 mm In this case apply the fire resistant PROMASTOP Coating with width of 50 mm The mass is placed between the strips of wool and between wool and damper housings c Place the fire damper B on the fire damper C and assemble them together on the front and back with use of perforated assembly strips 2 and self tapping screws M6x1...

Page 12: ...he openings in fire damper body In order to carry out the correct assembly 4 self tapping screws should be used per each assembly strip with length of 1200 mm c Fill the whole free space between the joint of fire dampers with non combustible mineral wool as shown in w1 NOTE The alternative way of wool mounting is to use two layers of wool with thickness of 30 mm In this case apply the fire resista...

Page 13: ...EP 1 a Fix the gasket on insulating spacer of one of adjoining fire dampers position 1 in the Figure 14 b Set together the sides of fire damper A and the fire damper B where the gasket was fixed and assemble them together on the front and back with use of perforated assembly strips 2 and self tapping screws M6x16 3 which should be tightened into the openings in fire damper body In order to carry o...

Page 14: ...ery size and its arrangement For vertical battery consisting of two KWP fire dampers B1 120 x H1 H2 180 Figure 15 For vertical battery consisting of three KWP fire dampers B1 120 x H1 H2 H3 240 Figure 16 For horizontal battery consisting of two KWP fire dampers B1 B2 180 x H1 120 Figure 17 For battery consisting of four KWP fire B1 B2 180 x H1 H2 180 Figure 18 b Put the battery of fire dampers int...

Page 15: ...Version 6 00 Date of editing 16 09 2022 r Page 14 z 18 Installation manual KWP O ES Figure 13 Installation of a battery consisting of two fire dampers KWP in vertical arrangement in ceiling ...

Page 16: ...Version 6 00 Date of editing 16 09 2022 r Page 15 z 18 Installation manual KWP O ES Figure 14 Installation of a battery consisting of three fire dampers KWP in vertical arrangement in ceiling ...

Page 17: ...Version 6 00 Date of editing 16 09 2022 r Page 16 z 18 Installation manual KWP O ES Figure 15 Installation of battery consisting of two fire dampers KWP in horizontal arrangement in ceiling ...

Page 18: ...Version 6 00 Date of editing 16 09 2022 r Page 17 z 18 Installation manual KWP O ES Figure 16 Installation of a battery consisting of four fire dampers KWP in ceiling ...

Page 19: ...75 0 400 53 9 63 8 73 7 83 0 92 6 98 0 112 7 122 6 131 9 141 8 152 0 177 7 188 5 199 1 500 72 2 83 5 94 1 105 5 116 2 127 5 138 5 149 9 160 2 171 2 199 8 211 5 223 2 600 80 2 92 6 104 7 117 1 129 2 142 0 154 1 166 5 178 9 191 3 222 0 235 5 248 7 700 88 4 102 0 115 2 14 9 142 9 156 8 163 1 176 0 197 3 211 1 247 6 264 9 282 5 800 96 6 111 8 125 8 141 3 155 9 170 9 186 1 200 7 215 7 230 6 266 0 281 6...