13.4.2.
Connection of double intake system, fixed lack of tightness opening
damper, TSS-X-24VDC, 24VDC peripheral device
Fig. 13.20. Detailed wiring diagrams of the double intake system (and the distribution damper system for the
base break assembly) to iSWAY FC, iSWAY RFC and the fixed inlet throttle to iSWAY FC, iSWAY WFC, iSWAY RFC
(optional output)
CABLE DESCRIPTION
DESIGNATION
CABLE SORT
CABLE TYPE
C1
HDGs FE180/PH90
3x1,5
CABLE DESCRIPTION
DESIGNATION
CABLE SORT
CABLE TYPE
C3
HDGs FE180/PH90
2x1,0
iSWAY-FC/-RFC device
iSWAY-FC/-WFC/-RFC device
Connection diagram of the double intake
to the SzA-FCP/-FCK cabinet (iSWAY-FC/-RFC device)
Connection diagram of the fixed lack of tightness opening damper
to the SzA-FCP/-FCK cabinet (iSWAY-FC/-WFC/-RFC device)
Belimo cable
Belimo cable
Belimo cable
Towards two
BELIMO BF24
actuators
Damper of the fixed lack
of tightness opening
BELIMO BF24
Intake auxiliary damper
–
PCR
with
BLE24 or BEN24 BELIMO actuator
Intake main damper
–
PCG
with
BLE24 or BEN24 BELIMO actuator