9
INPUTTING MOTOR DATA SAMPLE
1)
If the data in the drive doesn’t match the existing equipment, use
the following procedures to correct the values:
a)
Press
UP
arrow key to access the motor output power
parameter T2-04.
b)
Press
ENTER
key to view the default setting.
c)
Press
F1
(left),
F2
(right),
RESET
,
UP
and
DOWN
arrow keys to
enter the motor power nameplate data in kW – (kW) = (Motor
HP) x (.74)
i)
Example: 12 HP x .74 = 8.88 kW
(in this example T2-
04 would be 8.88)
d)
Press
ENTER
key to save the setting
e)
The display automatically returns to the display in Step 2.
2)
After verifying the data listed on the motor nameplate, press
UP
arrow key to confirm and get to “Tuning Ready” message.
3)
Press and hold down the M Contactor during the duration of the
Auto-Tune.
4)
Press
RUN
to activate Auto-Tuning.
Auto-Tuning finishes in approximately one to two minutes
Encoder Auto-Tuning
1
st
Phase Encoder Auto-Tuning
1)
Press
ENTER
key to select the value for T2-01.
2)
Set T2-01 to “
3
” and save the setting by pressing
ENTER
.
3)
Press and hold down the M Contactor.
4)
Press
RUN
to activate Auto-Tuning.
2
nd
Phase Encoder Auto-Tuning
1)
Press
ENTER
key to select the value for T2-01.
2)
Set T2-01 to “
4
” and save the setting by pressing
ENTER
.
3)
Press and hold down the M Contactor.
4)
Press
RUN
to activate Auto-Tuning.
** Remove the temporary jumper from drive H1 to REF. **
The Two-Phase Encoder Auto-Tunings finish very fast