MGC120 Petrol Genset Controller User Manual
MGC120 Petrol Genset Controller Version 1.2 2019-02-22 Page 7 of 20
4.3
PUSH BUTTONS
Table 4 Button Description
Icons
Function
Description
Stop/Reset
Stop the running genset both in manual mode and in auto mode, and
change controller to the manual mode.
In stop process, re-press this button to stop generator immediately.
In alarm status, press this button to reset any shutdown alarms.
In stop mode, press this button for more than 3s to test if the digital tube
and LED indicators are OK.
In parameter setting process, press this button to exit the setting.
Auto/Manual Switch
Increased value
Press this key, if auto indicator lights on, controller is in auto mode; if auto
indicator lights off, controller is in manual mode.
In parameter setting, press this key to downturn or increase the values.
Start
Decreased value
In manual mode, press this key to start genset.
In parameter setting, press this key to upturn or decrease the values.
Page Down
Changeover the display contents of digital tube.
Enter the parameter setting by pressing it for more than 3 second;
In parameter setting, it confirms the set information.
4.4
AUTO START/STOP OPERATION
Press
key and the indicator besides lights on, which means generator is in auto mode.
a) Auto Start Sequence
1) When remote start signal is active or mains failure(over/under voltage) delay is expired,
“Start
Delay” time is initiated;
2) When start delay is over, preheating relay outputs (if configured),
“preheat delay” is initiated;
3) After the above delay, the fuel relay outputs, and one second later, the start relay outputs;
During the starting time if the genset fails to start, fuel relay and start relay stop outputting, enter
“Crank Rest Time” and wait for next start;
4) If the genset fails to start during the set starting attempts, LED indicator will display start failure;
5) If the genset starts successfully during the starting attempts, it enters
“Safety On” time, during
which low oil alarm types are inactive; After
“Safety On” time, it enters “Start Idle Delay” (if
configured);
6)
During “Start Idle Delay”, under frequency and under volt alarms are inhibited; When this delay
is over, “Warming Up Delay” is initiated (if configured);
7)
After the “warming up delay”, genset will enter into Normal Running status. If genset voltage or
frequency is abnormal, controller alarm shutdown will be initiated.
b) Auto Stop Sequence
1) When remote start input is invalid or mains normal delay is expired,
“Stop Delay” time is
initiated;
2)
Once this “stop delay” has expired, the “Cooling Down Delay” is then initiated;
3) When
“Stop Idle Delay” (if configured) starts, idle speed relay outputs;
4) When
“ETS Solenoid Hold” begins, ignition control relay is energized and fuel relay is
de-energized; Genset enters standby status.