HPM6 Power Management Controller User Manual
Page 96 of
146
No.
Items
Range
Default
Description
13
Cooling Delay
(0-3600)s
0
High speed cooling time before stop
output.
14
Gen Insufficient Delay (0-3600.0)s
1.5
When current genset power can’t
meet load demand, alarm will be
initiated after delay.
15
Crank Success Delay
(0-3600.0)s
2.0
It is considered that crank success
after conditions are met and delay
continues in crank rest, then it enters
stable load after crank rest is over.
16
Fast Start Delay
(0-3600)s
2
Time from auto fast start conditions
are active to start output rest.
17
Fast Stop Delay
(0-3600)s
2
Time from auto fast stop conditions
are active to stop output rest.
18
SG-DG Max.
Grid-connection Time
(0-3600.0)s
60.0
The max grid-connection time of SG
and DG, alarm will be initiated when
the time is over.
12.6
ANALOG INPUT PORTS SETTING
Table 32 – Analog Input Ports Setting
No.
Items
Range
Default
Description
Analog Input Ports Setting
Analog Input Port 1
1
Function
(0-4)
0
0: Not Used
1: Fixed Active Power Input
2: Fixed Reactive Power Input
3: HC Feedback Input
4: Temperature Sensor
2
Type
(0-2)
0
0: Resistance Type
1: Current Type
2: Voltage Type
3
Input Min. Value
(0.0-1000.0)Ω/mA/V 0.0
Unit is changed according to
type.
4
Input Max Value
(0.0-1000.0)Ω/mA/V 600.0
5
HC Feedback Range
(0-60000)kW
100
6
Open Action
(0-6)
1
7
Curve Type
(0-15)
0
8
Upper
Limit 1
Action
(0-1)
0: Disable
9
Auto ACK
(0-1)
0: Disable
10
Alarm
Self-lock
(0-1)
0: Disable
11
Threshold
(0.0-1000.0)°C
100.0
12
Return Value (0.0-1000.0)°C
90.0