3.5
POWER MANAGEMENT FUNCTIONS
Plant operation:
●
Diesel generator supply (up to 16 generators)
●
Shore power supply (all gensets are inhibit to start and take on load)
Power management functions:
●
Blackout handling
●
Load-dependent start/stop
●
Auto start mode selection
►
Cyclic start
►
Linear start
►
Duty time start
●
Auto scheduled start mode selection
►
Genset power percentage
►
Left power
●
Priority Trip
●
Heavy consumer
●
Light consumer
●
Reserved number of running gensets
●
Safety stop, safety trip
●
Safety mode (reserve an additional unit running on load)
●
Limit network-connected gensets numbers
●
Busbar breaking handle
4.
SPECIFICATION
Table 3 – Specification Parameters
Parameter
Content
Working Voltage
DC8. 0V to 35. 0V, continuous power supply
Overall Consumption
<4W (Standby mode: ≤2W)
AC Input:
3 Phase 4 Wire
3 Phase 3 Wire
2 Phase 3 Wire
Single Phase
AC15V - AC360V (ph-N)
AC30V - AC620V (ph-ph)
AC15V - AC360V (ph-N)
AC15V - AC360V (ph-N)
Alternator Frequency
50Hz/60Hz
Flexible Relay Output
8A AC250V volts free output
GOV
DC(-10~10)V/(-20~20)mA
AVR
DC(-10~10)V /(-20~20)mA
FREQ IN
DC(-10~10)V
VOLT IN
DC(-10~10)V
Case Dimensions
266mm x 182mm x 45mm
Panel Cutout
214mm x 160mm
CT Secondary Current
Rated 5A