HGM9530 GENSET PARALLEL UNIT USER MANUAL
HGM9530 Genset Parallel Unit 2016-11-03 Version 1.4 Page 11 of 65
5.2 PUSHBUTTONS
Icons
Keys
Description
Stop
Stop running generator in Auto/Manual mode; Lamp test (press
at least 3 seconds); Reset alarm in stop mode; During stopping
process, press this button again to stop generator immediately.
Start
Start genset in
Manual
mode.
Manual Mode
Press this key and controller enters in
Manual
mode.
Auto Mode
Press this key and controller enters in
Auto
mode.
Mute/Reset Alarm
Alarming sound off; If trip alarm occurs, pressing the button at
least 3 seconds can reset this alarm.
Close
Close breaker in manual mode.
Open
Open breaker in manual mode.
Up/Increase
1) Screen scroll;
2) Up cursor and increase value in setting menu.
Down/Decrease
1) Screen scroll;
2) Down cursor and decrease value in setting menu.
Left
1) Screen scroll;
2) Left move cursor in setting menu.
Right
1) Screen scroll;
2) Right move cursor in setting menu.
Set/Confirm
Select viewing area.
Exit
1)Return to main menu;
2) Return to previous menu in setting menu.
NOTE
: Press
and
simultaneously in manual mode will force generator to crank.
Successful start will not be judged according to crank disconnect conditions, operator will have to crank
the starter motor manually; when operator decides that the engine has fired, he/she should release the
button and start output will be deactivated, safety on delay will be initiated.
WARNING:
Default password is 00318, user can change it in case of others change the advanced
parameters setting. Please clearly remember the password after changing. If you forget it, please
contact SmartGen services and send all information in the controller page of “
ABOUT
” to us.