HGM8151 Genset Parallel Controller User Manual Page 35 of 66
7.2
DEFINED CONTENTS OF PROGRAMMABLE OUTPUT PORTS
7.2.1
DEFINED CONTENTS OF PROGRAMMABLE OUTPUT PORTS
Table 13 Defined Contents of Programmable Output Ports
No.
Type
Description
0
Not Used
1
Custom Period 1
Details of function description please see the following.
2
Custom Period 2
3
Custom Period 3
4
Custom Period 4
5
Custom Period 5
6
Custom Period 6
7
Custom Combined 1
8
Custom Combined 2
9
Custom Combined 3
10
Custom Combined 4
11
Custom Combined 5
12
Custom Combined 6
13
Reserved
14
Reserved
15
Reserved
16
Reserved
17
Air Flap Control
Action when over speed shutdown and emergence stop. It
also can close the air inflow to stop the engine as soon as
possible.
18
Audible Alarm
Action when warning, shutdown, trips. Can be connected to
announciator externally. When
“alarm mute” configurable
input port is active, it can remove the alarm.
19
Louver Control
Action when genset starting and off when genset stopped
completely.
20
Fuel Pump Control
It i
s controlled by fuel pump of level sensor’s limited
threshold.
21
Heater Control
It is controlled by
heating of temperature sensor’s
limited
threshold.
22
Cooler Control
It is controlled by cooler of temperature sensor’s
limited
threshold.
23
Oil Pre-supply Output
Action from “crank on” to “safety on”.
24
Generator Excite
Output in start period. If there is no generator frequency
during hi-speed running, output for 2 seconds again.
25
Pre-lubricate
Actions in period of pre-heating to safety run.
26
Remote Control Output
This port is controlled by communication (PC).
27
GSM Power Supply
It is used for supply power for GSM module (power off and
reset GSM module when GSM fail to communication)