HGM7110DC Genset Controller
HGM7110DC Genset Controller Version: 1.0 2014-09-27 Page
47
of
68
8.3 PROGRAMMABLE INPUT PORTS (ALL ACTIVE WHEN
CONNECT TO GRAND (B-))
Form 3
No.
Type
Description
0
Users Configured
Including following functions,
Indication: indicate only, not warning or shutdown.
Warning: warn only, not shutdown.
Shutdown: alarm and shutdown immediately
Trip and stop: alarm, generator unloads and shutdown
after hi-speed cooling
Trip: alarm, generator unloads but not shutdown.
Never: input inactive.
Always: input is active all the time.
From crank: detecting from generator start.
From safety on: detecting after safety on delay.
1
Reserved
2
Alarm Mute
Can prohibit “Audible Alarm” output when input is active.
3
Reset Alarm
Can reset shutdown alarm and trip alarm when input is
active.
4
Reserved
5
Lamp Test
All LED indicators are illuminating when input is active.
6
Panel Lock
All buttons in panel is inactive except
and
there is
in the right of first row in LCD when input is
active.
7
Reserved
8
9
Inhibit Auto Stop
In Auto mode, during generator normal running, when
input
is
active,
prohibit
generator
shutdown
automatically.
10
Inhibit Auto Start
In Auto mode, prohibit generator start automatically
when input is active.
11
Inhibit Scheduled
In Auto mode, prohibit fixed timing start genset when
input is active.
12
Reserved
13
Aux Gen Closed
Connect generator loading switch’s auxiliary point.
14
Inhibit Gen Load
Prohibit genset switch on when input is active.
15
1#Acc.Load Closed
Connect to the load
switch’s auxiliary point of 1#
Accumulator.
16
2#Acc.Load Closed
Connect to the load
switch’s auxiliary point of 2#