HGM7110DC Genset Controller
HGM7110DC Genset Controller Version: 1.0 2014-09-27 Page
31
of
68
8 SCOPES AND DEFINITIONS OF PROGRAMMABLE PARAMETERS
8.1 CONTENTS AND SCOPES OF PARAMETERS
Form 1
No.
Items
Parameters
Defaults
Description
Charge Setting
1
Acc. 1# Rated
Voltage
(0-75) V
48
The rated voltage of 1#accumulator.
2 1# Cell Count
(1-50)
24
The battery number of 1#accumulator.
3
1#
Under
Voltage Warn
(0-1)
0
0: Disable; 1: Enable
(0-1000) %
95
Set Value
(0-1000) %
98
Return Value
(0-3600) s
5
Delay
4
1#
Over
Voltage Warn
(0-1)
0
0: Disable; 1: Enable
(0-1000) %
115
Set Value
(0-1000) %
112
Return Value
(0-3600) s
5
Delay
5
1#
Under
Voltage Stop
(0-1)
0
0: Disable; 1: Enable
(0-1000) %
92
Set Value
(0-3600) s
5
Delay
6
1#
Over
Voltage Stop
(0-1)
0
0: Disable; 1: Enable
(0-1000) %
118
Set Value
(0-3600) s
5
Delay
7
Acc. 2# Rated
Voltage
(0-75) V
48
The rated voltage of 2#accumulator.
8 1# Cell Count
(1-50)
24
The battery number of 2#accumulator.
9
2#
Under
Voltage Warn
(0-1)
0
0: Disable; 1: Enable
(0-1000) %
95
Set Value
(0-1000) %
98
Return Value
(0-3600) s
5
Delay
10
2#
Over
Voltage Warn
(0-1)
0
0: Disable; 1: Enable
(0-1000) %
115
Set Value
(0-1000) %
112
Return Value