HEM4300 Engine Controller User Manual Page 52 of 55
13.4
CUMMINS QSZ13
Table 22 Engine OEM Connector
Terminals of controller
OEM connector of engine
Remark
Aux. output 1
45
Oil injection switch. Configure it as “Fuel
Output”.
Aux. output 2
-
Configure it as “Crank Output”. Connect to
starter coil directly via expand relay.
CAN(H)
1
Using twisted-pair shielded line with single
end grounded.
CAN(L)
21
Engine type: Cummins-QSZ13.
13.5
DEUTZ EMR2
Table 23 F Connector
Terminals of controller
F connector
Remark
Aux. output 1
Expansion
30A
relay,
providing battery voltage
for 14; Fuse is 16A.
Configure it as “Fuel Output”.
Aux. output 2
-
Configure it as “Crank Output”. Connect to
starter coil directly via expand relay.
-
1
Connect to battery negative pole.
CAN(H)
12
Using twisted-pair shielded line with single
end grounded.
CAN(L)
13
Engine type: DEUTZ-EMR2.
13.6
MTU ADEC (SMART MODULE)
Suitable for MTU engine with ADEC (ECU8) and SMART module.
Table 24 ADEC (X1 Port)
Terminals of controller
ADEC (X1port)
Remark
Aux. output 1
X1 10
Configure it as “Fuel Output”.
X1 Terminal 9 connected to negative of
battery.
Aux. output 2
X1 34
X1 Terminal 33 connected to negative of
battery.
Table 25 ADEC (X4 Port)
Terminals of controller
SMART (X4 port)
Remark
CAN(H)
X4 1
Using twisted-pair shielded line with single
end grounded.
CAN(L)
X4 2
Engine type: MTU-ADEC.