HAT600N Series ATS Controller User Manual 

HAT600N  Series  ATS  Controller                      Version  1.1                  2019-09-05                Page  7  of  24

 

1# Volt normal 

2# Volt normal 

Gens Start signal Out 

Gens starting 

PWR      329kW   

PF 1.00      PS    329kVA 

2010-06-10 (4) 20:25:36

 

Present Status:

 

MANUAL

 

5.  LCD DISPLAY 

5.1  MAIN SCREEN 

 

This screen shows:    line-line voltage (L1-L2, L2-L3, and 
L3-L1),  frequency 

and  controller’s  present  working 

mode. 

   

This screen shows: 1# and 2# 3 phase Voltage (L-N), 3 
phase current with load and controller status. 

 
 

 

 

 

This  screen  shows:  total  active  power,  total  apparent 
power,  power  factor  and  real-time  clock  and  controller 
working status. 

                     

First line: 1# operating state of power supply. 
Second line: 2# operating state of power supply. 
Third line: other operating states.   
Fourth line: alarm type and information. 

Table 5 Display of #1 Status (upper to lower) 

No. 

Item 

Type 

Description 

1# Gens Alarm 

Alarm 

When 1# genset occur failure, this will display. 

1# Fail to Close 

Alarm 

When  1#  breaker  occur  closing  failure,  this  will 
display. 

1# Fail to Open 

Alarm 

When  1#  breaker  occur  opening  failure,  this  will 
display. 

1# Over Voltage 

Indication 

When  1#  power  supply  voltage  is  higher  than  the 
setting value, this will display. 

1# Miss Phase 

Indication 

Loss of any phase of A, B and C. 

1# Over Freq 

Indication 

When 1# power supply frequency is higher than the 
setting value, this will display. 

1# Under Freq 

Indication 

When 1# power supply frequency is lower than the 
setting value, this will display. 

1# Under Volt 

Indication 

When  1#  power  supply  voltage  is  lower  than  the 
setting value, this will display. 

1# reverse phase 

Warning 

Phase sequence is not A-B-C. 

10 

1# Volt Normal 

Indication 

1# source voltage is within the setting range. 

 

 

U1(L-L) 380    380    380V               

U2(L-L) 380    380    380V 

F1 50.0Hz      F2 50.0Hz                         

Present Status: MANUAL 

               

U1(L-N) 219    219    219V 

U2(L-N) 219    219    219V     

AMP      500    500    500A

 

Present Status: MANUAL 

 

                 

Summary of Contents for HAT600N Series

Page 1: ...HAT600N SERIES HAT600N HAT600NI HAT600NB HAT600NBI ATS CONTROLLER USER MANUAL SMARTGEN ZHENGZHOU TECHNOLOGY CO LTD...

Page 2: ...ing or storing in any medium by electronic means or other without the written permission of the copyright holder Applications for the copyright holder s written permission to reproduce any part of thi...

Page 3: ...TION 5 4 OPERATING 6 5 LCD DISPLAY 7 6 COMMISSIONING 9 7 PARAMETERS CONFIGURATION 10 8 EVENT LOG 14 9 TIMING START 15 10 DATE AND TIME SETTING 15 11 LANGUAGE SETTING 15 12 CONTROLLER INFORMATION 16 13...

Page 4: ...cy F2 4 Measure and display load active power apparent power power factor and 3 phase current 5 Over current alarm function 6 Over under voltage loss of phase reverse phase sequence over under frequen...

Page 5: ...3P4W L L 80 625 V 80 480 V 3P3W L L 80 625 V Not used 1P2W L N 50 360 V 50 280 V 2P3W A B 80 625 V 80 480 V Rated Frequency 50 60Hz Close Open Trip Relay Output 16A AC250V Free Voltage relay output Pr...

Page 6: ...off 1 or 2 power to off load 2 Close In Manual mode switch on 2 power to load Manual Press and controller enters into Manual mode Automatic Press and controller enters into AUTO mode Test Pressing thi...

Page 7: ...Type Description 1 1 Gens Alarm Alarm When 1 genset occur failure this will display 2 1 Fail to Close Alarm When 1 breaker occur closing failure this will display 3 1 Fail to Open Alarm When 1 breake...

Page 8: ...hase sequence is not A B C 10 2 Volt Normal Indication 2 source voltage is within the setting range Table 7 Display Status of Other Items upper to lower No Item Type Description 1 Trip alarm Alarm Tri...

Page 9: ...s normal or not STOP TO TEST The start generator signal will turn off after pressing this key immediately CYCLE START When this mode is active generator start signal will cyclic output according to ma...

Page 10: ...l to voltage abnormal 03 2 Normal Delay 0 9999 s 10 It is the delay of 2 power from voltage abnormal to voltage normal 04 2 Abnormal Delay 0 9999 s 5 It is the delay of 2 power from voltage normal to...

Page 11: ...23 Under Frequency Return 0 0 75 0 Hz 48 0 Normal return value of over frequency 24 CT Ratio 5 65000 5 500 Current Transformer ratio 25 Rated Load Current 5 6000 A 500 Load rated current 26 Over Curre...

Page 12: ...7 3 INPUT OUTPUT FUNCTION DESCRIPTION Table 9 Input Port Function Description Item Description 01 Not used Invalid 02 Breaking compulsorily When active this will force the breaker to transfer the ATS...

Page 13: ...09 2 Abnormal volt It will output when 2 voltages is abnormal 10 Over current output It will output when loaded current exceeds the limit 11 Auto state output In will show output in automatic mode 12...

Page 14: ...it can display the record information circularly including the temporal voltage of 1 and 2 detailed voltage current frequency and date and time Press and it will exit the current interface while pres...

Page 15: ...ime Generator continuously run time can be set on the duration of maximum time for 99 hours 59 minutes 10 DATE AND TIME SETTING In the main screen press key and select 4 Date Time set and then press k...

Page 16: ...0 2009 10 11 12 CONTROLLER INFORMATION In the main screen press key and select 6 Controller information and then press key the screen will show the controller information interface as follow Display c...

Page 17: ...UPPLY The power of ATS is smartly controlled by controller As long as one power is normal it can ensures ATS voltage power supply normally and can be transferred properly Users should select power sup...

Page 18: ...can also be applicable to dual power switching management for factories telecom industrial and civil buildings achieving remote control remote measuring remote communication functions More information...

Page 19: ...gative DC negative input 20 B To start engine connect the terminal to battery positive DC positive input 8 35 V controller power supply 21 1 close input Detection of 1 switch closing state voltage fre...

Page 20: ...HAT600N Series ATS Controller User Manual HAT600N Series ATS Controller Version 1 1 2019 09 05 Page 20 of 24 16 TYPICAL WIRING DIAGRAM Fig 3 ATYS3 Wiring Diagram Fig 4 SGQ N T Wiring Diagram...

Page 21: ...HAT600N Series ATS Controller User Manual HAT600N Series ATS Controller Version 1 1 2019 09 05 Page 21 of 24 Fig 5 SGQ M Wiring Diagram Fig 6 VITZRO Wiring Diagram...

Page 22: ...HAT600N Series ATS Controller User Manual HAT600N Series ATS Controller Version 1 1 2019 09 05 Page 22 of 24 Fig 7 Contactor Wiring Diagram Fig 8 ATYSM3S Wiring Diagram...

Page 23: ...9 09 05 Page 23 of 24 Fig 9 Breaker Wiring Diagram Remark all above are application diagrams of HAT600N series ATS controllers However HAT600N and HAT600NB have no current sample input please skip ove...

Page 24: ...ntroller with RS485 converter GND or PC GND It is recommended that a 120 resistor is added between A and B of RS485 Programmable output error Check programmable output connections and pay attention to...