HAT530P/HAT530PC Series ATS Controller User Manual Page 11 of 18
No
.
Item
Range
Default
Description
the set value.
17 Under voltage
(70-100)%
75
Voltage lower limit; it is abnormal when
the voltage is below the set value.
18 Under Volt Return
(70-100)%
77
Voltage lower limit return value; it is
normal only when the voltage is over the
set value.
19 Over Freq. Enable
(0-1)
0
0: Disable
;
1: Enable
20 Over Frequency
(100-120)% 110
Frequency upper limit; it is abnormal
when the frequency is over the set value.
21 Over Freq. Return
(100-120)% 104
Frequency upper limit return value; it is
normal only when the frequency is below
the set value.
22 Under Freq. Enable (0-1)
0
0: Disable
;
1: Enable
23 Under Frequency
(80-100)%
90
Frequency lower limit; it is abnormal
when the frequency is below the set
value.
24 Under Freq. Return (80-100)%
96
Frequency lower limit return value; it is
normal only when the frequency is over
the set value.
25 Loss of Phase
(0-1)
1
0: Disable
;
1: Enable
26
Reverse
Phase
Sequence
(0-1)
0
0: Disable
;
1: Enable
27 Master-Slave Set
(0-2)
0
0. 1# Master;
1. 2# Master;
2. Each Backup
28
Auto Trans. Auto
Restore Set
(0-1)
1
0: Auto Trans. Non Restore
1: Auto Trans. Auto Restore
29 Neutral Position
(0-1)
0
0. With Breaking;
1. Without Breaking
30 Module Address
(1-254)
1
Communication address for module.
31 Stop Bit Setting
(0-1)
0
0: 1 stop bit;
1: 2 stop bits.
NOTE 1:
Parameters above are configured via PC software of SmartGen. The PC programming connection is to use
RS485 interface of SG72 module connecting with RS485 interface of controller.
NOTE 2
: “1# Voltage Normal Delay” and “2# Voltage Normal Delay” can be set only via the potentiometer which
locates nearby the back panel terminal. “1# Voltage Abnormal Delay” and “2# Voltage Abnormal Delay” can be set via the
PC software or potentiometer which locates nearby the back panel terminal. AC system setting and master selection
priority can be set via panel button or PC software while other parameters can be set via PC software only.
NOTE 3
: S1 Normal Delay set value must be no less than S1 Abnormal Delay, otherwise, S1 Normal Delay set value
will be forced to set as S1 Abnormal Delay set value. S2 Normal Delay set value must be no less than S2 Abnormal Delay,
otherwise, S2 Normal Delay set value will be forced to set as S2 Abnormal Delay set value.