HAT530 ATS CONTROLLER
HAT530 ATS CONTROLLER 2014-06-23 Version 1.0 Page 18 of 26
6.2 OUTPUT FUNCTION DESCRIPTION
The output port function as below,
Items
Description
00. Not used
Invalid.
01. 1# Normal volt
It will output when1# voltage is normal.
02. 1# Abnormal volt
It will output when 1# voltage is abnormal.
03. 2# Normal volt
It will output when 2# voltages is normal.
04. 2# Abnormal volt
It will output when 2# voltages is abnormal.
05.1#2# Abnormal volt
It will output when 1#2# voltages are abnormal
simultaneously.
06. Auto Mode
In will output in automatic mode.
07. Manual Mode
In will output in manual mode.
08. Gens start (N/O)
When generator starts output (Relay closed).
09. Gens start (N/C)
When generator starts output (Relay released).
10. 1# Close Output
1# Switch ON signal output.
11. Open Output
Switch OFF signal output.
12. 2# Close Output
2# Switch ON signal output.
13. Reserved
14. Reserved
15. Reserved
16. 1# Close Status Output
The close status of 1# switch.
17. 2# Close Status Output
The close status of 2# switch.
18. Reserved
19. Reserved
20. ATS Power A Phase
ATS power supply.
21. ATS Power B Phase
22. ATS Power C Phase
23. ATS Power N Phase