HAT530 ATS CONTROLLER
HAT530 ATS CONTROLLER 2014-06-23 Version 1.0 Page 15 of 26
6 PROGRAMMED PARAMETER AND RANGE
6.1 PARAMETERS TABLE
No.
Item
Range
Default
Description
01
1#
Normal
Delay
(0-60)s
Can be set
via controller
potentiometer
It is the delay of #1 power from
voltage
abnormal
to
voltage
normal. Generally, it is 10s.
02
1# Abnormal
Delay
(0-60)s
5
It is the delay of #1 power from
voltage
normal
to
voltage
abnormal.
03
2#
Normal
Delay
(0-60)s
Can be set
via controller
potentiometer
It is the delay of #2 power from
voltage
abnormal
to
voltage
normal. Generally, it is 10s.
04
2# Abnormal
Delay
(0-60)s
5
It is the delay of #1 power from
voltage
normal
to
voltage
abnormal.
05 Close Delay (0-20)s
5
Closing relay output pulse. If set
as zero, it is continuous output.
06
Open Delay
(1-20)s
5
Open relay output pulse.
07
Transfer
Interval
(0-60)s
1
It is the delay from 1# power open
to 2# power close or from 2#
power open to 1# power close.
08
Exceed
Transfer
(0-20.0)s
0.0
It is the extra output delay of the
close relay after the closing signal
has received.
09 Start Delay
(0-3600)s
1
When voltage is abnormal, start
delay begins; start signal is
initiated after the delay has
expired.
10 Stop Delay
(0-3600)s
90
When starting, if the mains
voltage is normal, stop delay
begins; stop signal is initiated
after the delay has expired.
11
AC System
(0-2)
0
0. 3-phase 4 wires
1. 2-phase 3 wires
2. Single phase 2 wire
12
Rated Volt
(100-240)V
230
AC system rated voltage.
13
Rated
Frequency
(50.0-60.0)Hz
50.0
To offer standards for detecting of
over/under frequency.
14
Over
Volt
Enable
(0-1)
1
0: Disable
;
1: Enable
15
Over
Voltage
(100-120)%
115
Voltage upper limit; it is abnormal
when the voltage has exceed the
set value.