CMM366B-4G/CAN-4G Cloud Monitoring Communication Module User Manual
CMM366B-4G/CAN-4G Cloud Monitoring Communication Module 2020-03-10 Version 1.0 Page 12 of 19
Table 6
– Digital Input Ports Content
No.
Item
Description
0
Not Used
Not used.
1
Lamp Test
All the indicators are illuminated when input is active.
2
Remote Control Inhibited
Cloud start/stop control is prohibited when input is active.
3
Access Alarm Input
Access alarm is uploaded to server when input is active.
4
Fire Alarm Input
Fire alarm is uploaded to server when input is active.
5
Alarm Input
External alarm is uploaded to server when input is active.
6
Reserved
7
Reserved
8
Reserved
9
Factory Test Mode
It is only used for factory test when active.
5.2
PC CONFIGURATION INTERFACE
Connecting the USB port of CMM366B-4G/CMM366CAN-4G communication module with PC to
configure the parameters.
Fig. 11 - Gateway Configuration
Fig. 12 - Module Monitoring Interface