3 SPECIFICATION
Table 2
– Technical Data
Items
Contents
Operating Voltage
DC 8.0V~35.0V, continuous power supply.
Power Consumption
Standby:
≤2W
Working: ≤5W
Auxiliary Input
Digital Input, connect (B-) is active.
Auxiliary Output
1A DC30V Volts free output
USB Host
A-type USB female port
RS485
Isolated type
RS232
General type
LINK
SmartGen exclusive port
USB Device
B-type USB female port
GPRS Port
Standard SMA port (female), SMA port (male) for antenna
GPS Port
Standard SMA port (female), SMA port (male) for antenna, active antenna
Wireless Network
WCDMA 3G GPRS 2G
Case Dimensions
72.5mmx105mmx34mm
Working Conditions
Temperature: (-25
~
+70)°C
Humidity: (20
~
93)%RH
Storage Condition
Temperature: (-25
~
+70)°C
Weight
0.15kg