![Smartgen BACM1206 User Manual Download Page 11](http://html.mh-extra.com/html/smartgen/bacm1206/bacm1206_user-manual_1297446011.webp)
BACMXX06 Series Battery Charger
BACMXX06 Series Battery Charger Version 1.0 2014-12-20 Page 11 of 18
Under Voltage
Delay
120s
(0~3600)s
“Under voltage” alarm
will be initiated if the
battery voltage has fallen
below the set value and
the delay timer has
expired.
Under Voltage
Return Value
24.0V
12.0V
(16.0~30.0)V
(8.0~15.0)V
The transition voltage
from
“under voltage”
transfer to
“normal
voltage
”.
Under Voltage
Return Delay
10s
(0~3600)s
“Under voltage” alarm
will be removed if the
battery voltage has
exceeded the return
value and the delay timer
has expired.
Temperature
Sensor
1
(0~1)
0: Disable; 1: Enable
Temperature
Compensation
1
(0~1)
0: Disable; 1: Enable
Temperature
Compensation
Set Value
0.036V/
℃
0.018V/
℃
(0.020~0.060)
V/
℃
(0.010~0.030)
V/
℃
The Compensation of
every 1
℃
change on
20
℃
basis.
High Temp.
Warn
1
(0~1)
0: Disable; 1: Enable
High Temp. Set
Value
55
℃
(0~80)
℃
“High Temp.” alarm will
be initiated if the battery
temperature has
exceeded the set value.
High Temp.
Delay
0.5s
(0~60.0)s
“High Temp.” alarm
will be initiated if the
battery temperature
has exceeded the set
value and the delay
timer has expired.
High Temp.
Return Value
50
℃
(0~80)
℃
The transition
temperature from
“High
Temp.
” transfer to
“Normal Temp.”.
High Temp.
Return Delay
1s
(0~60.0)s
“High Temp.” alarm
will be removed if the
battery temperature
has fallen below the
return value and the
delay timer has
expired.
Auxiliary Input
Port
3
(0~3)
0
、
Not Used
;
1
、
Shutdown
:
The
battery charger enters
into Standby Status if