Form #146 (02.16)
151 Memorial Drive, Unit H - Shrewsbury, MA 01545 - Phone: (888) 792-2223 - [email protected] - www.plastixs.com
Tracer
®
Electronic Switching
Flowmeter
with FCI
(Fluid Characteristic Indication)
Operating Instructions (Ver 5.1)
General
The Tracer Electronic Switching Flowmeter provides:
◆
0 to 5V or 0 to 10V Selectable Flow Output
◆
0 to 5V or 0 to 10V Selectable Temperature Output
◆
1A, 30VAC/42VDC Programmable Switch for high
or low temperature and/or flow
◆
Fluid Flow Rate Display in gallons per minute
(gpm) or liters per minute (lpm)
◆
Fluid Temperature Display (°F or °C)
◆
BTU’s per Minute Display
◆
Fluid Characteristic Indication (Turbulent Flow or
“TFLOW” on display)
BTU Basics
To obtain the most accurate BTU calculation, use the Tracer
to measure the supply side water temperature (in °F) before
installing the Tracer in a cooling water return line.
BTU’s per minute calculation is based on the increase in water
temperature multiplied by the flow rate. The Tracer Electronic
Flowmeter calculates this information based on supply side
temperature entered manually. Due to inherent differences in most
thermometers, the most accurate BTU calculation will result from
using the same thermometer (inside the Tracer) to measure supply
and return line temperatures. Record the supply side temperature and
enter it using the “Set BTU/m Input Temperature” instructions on
page 3.
Turbulent Flow
“TFLOW” notification appears on the display when Turbulent Flow
is likely inside the cooling circuit of the selected size.
Turbulent flow is the mixing and swirling of water inside a cooling
line that provides optimum heat transfer. Water flow rate greater than
the point of Turbulent Flow does not provide a proportional benefit.
Turbulent flow tracking allows technicians to apply mathematical
cooling principles to all machines in a water system. Visit the
Technical Documents section of www.smartflow-usa.com for a
detailed discussion of Turbulent Flow.
Input the percentage of glycol in cooling water (0%, 10%, 20% or
30%) for accurate Turbulent Flow Indication. See Setup Mode option
on page 5. Antifreeze compounds of ethylene or propylene glycol are
sometimes added to cooling waer. Glycol compounds have
substantially higher viscosity than water. As a result, higher flow
rates are required to reach Turbulent Flow when glycol is used.
Temperature
Operating Range............32 to 180°F (0 to 82°C)
Accuracy........................±2% of Display Value
Repeatability..................±1% of Display Value
Component Materials
Body (3/8" model).........Nickel-Plated Brass
Body (3/4" thru 2")........Anodized Aluminum
Stainless Steel (optional)
Back Cover(3/8" only) ..Polysulfone
Impeller..........................Nylon 6/12
Magnet...........................Neodymium
Shaft...............................18-8 Stainless Steel
Electronics Cover ..........Nylon 6/6
Cable..............................9-Conductor, 24AWG
Operating
Internal Relay ................SPDT 1A, 30VAC/42VDC
Power Required .............8 to 28VDC
Maximum Pressure........100psi (7bar)
Application
Liquid running through the Tracer flowmeter
should be free of metal shavings. Loose
particles can interfere with moving
components causing extra maintenance
requirements.
Specifications
Flow
Accuracy ....................±5% of Full Range
Repeatability ..............±3% of Full Range
Environment
Tracer construction is water resistant, but the
electronics housing is not submersible.
Size [NPT(F)]
Range (gpm)
Range (lpm)
3/8"
0.5 to 8
0 to 30
3/4"
2.0 to 20
8 to 76
1"
3.0 to 30
11 to 114
1-1/2"
6.5 to 60
25 to 228
2"
10.0 to 110
38 to 418
U.S. Patent No.
7,729,869