Longo programmable controller LPC-2.CH1M
4.3 Mounting instructions
Figure 4: Housing dimensions
Dimensions in millimeters.
All connections, module attachments and assembling must be done while
module is not connected to the main power supply.
Module should not be mounted outdoors.
Module should be positioned in the wall inside of the room. Avoid direct
sunlight or positioning near heating/cooling source object.
Several RFID panels should not be mounted close to each other. Minimum
distance to next panel is at least 30 cm. This restriction also applies in
case of mounting panels on both sides of the same wall. Adequate shielding
material and provisions could be used to avoid interference between
panels.
RFID panel should not be positioned close to conductive areas (e.g.: metal
frames and metal cover plate).
Mounting instructions:
1. Set the correct RS-485 address (S1 switch) for LPC-2.CH1M (refer to the Table 4).
2. Connect interconnection cable to the connector K1. Max. allowed tractive force is 30 N.
3. Put the LPC-2.CH1M in mounting frames.
4. Cover LPC-2.CH1M with cover plate.
LPC-2.CH1M connects to the main module on its RS-485 port using interconnection cable. When more
special modules (e.g. LPC-2.CR1, LPC-2.CH1, LPC-2.DP1) are connected to main module, splitter is
also required (e.g. SPL-2).
NOTE
: Signal wires must be installed separately from power and high voltage wires in accordance
with general industry electrical installation standard.
7