Apply power to the WZM.

The green power LED will illuminate. 

The other LEDs should be extinguished. 

The screen should also display ‘System Normal’.

  15  

Apply power

NOTE: This product contains relays which when subjected to mechanical shock may cause 

momentary transitions from the currently active state. The transitions will be less than 1 second 

and any equipment connected must not respond to such momentary changes of the relay. This 

product should be fixed to a stable and secure structure that is not subject to severe mechanical 

shock.

POWER

   SmartCell WZM

   System Normal
01/01/00     Access

   SmartCell WZM

   System Normal
01/01/00     Access

The system can now be programmed. 

Refer to the WZM programming Guide (MK067) for details of 

compatible SmartCell devices and full programming 

information.

  16  

Configuration

Summary of Contents for SC-13-1100-0001-99

Page 1: ...2021 EMS Ltd All rights reserved TSD127 0001 99 Issue 1 05 05 2021 AJM FIRE FAULT POWER FUNCTION 1 FUNCTION 2 1 2 3 4 Intelligent Wireless Zone Monitor Wireless Control Panel Installation Guide...

Page 2: ...ent Wireless Zone Monitor WZM allows for 16 wireless devices to be added to Conventional or Addressable fire systems Typical addressable fire system connection Typical conventional fire system connect...

Page 3: ...he procedures outlined in this installation guide must be carefully followed The installation must conform to applicable local installation codes and should only be installed by a fully trained compet...

Page 4: ...3 2 4 For additional information refer to TSD032 EN54 4 UNIVERSAL PSU SC 60 1000 INPUT 220 240VAC 50Hz 0 3A OUTPUT 5 0 8 5VDC 0 8A MAX STATUS FAULT MAINS CHARGER FAIL BATTERY LOW BATTERY FAIL START I...

Page 5: ......

Page 6: ...ly closed operation as required SKIP THIS STEP IF CONNECTING TO A CONVENTIONAL FIRE SYSTEM BAT ENABLE TAMPER RESET AERIAL A AERIAL B ATTENTION ELECTROSTATIC SENSITIVE DEVICE RS232 EN54 4 UNIVERSAL PSU...

Page 7: ...tion BAT ENABLE TAMPER RESET AERIAL A AERIAL B ATTENTION ELECTROSTATIC SENSITIVE DEVICE RS232 EN54 4 UNIVERSAL PSU SC 60 1000 INPUT 220 240VAC 50Hz 0 3A OUTPUT 5 0 8 5VDC 0 8A MAX STATUS FAULT MAINS C...

Page 8: ...ault mains fault and Gen Fault general battery fault If a fault input GEN FAULT or M FAULT is not being used leave the link as factory fitted 10 Connection wiring 230 VAC version only 24 VDC Dual Outp...

Page 9: ...PSU SC 60 1000 INPUT 220 240VAC 50Hz 0 3A OUTPUT 5 0 8 5VDC 0 8A MAX STATUS FAULT MAINS CHARGER FAIL BATTERY LOW BATTERY FAIL START INPUT L N For additional information refer to TSD042 0359 CPR 00267...

Page 10: ...MAX STATUS FAULT MAINS CHARGER FAIL BATTERY LOW BATTERY FAIL START INPUT L N E For additional information refer to TSD042 0359 CPR 00267 15 0905 SLIDETO REMOVE EOL SOUNDER A L1 L1 L2 EOL ALARM L1 L1 L...

Page 11: ...ansitions from the currently active state The transitions will be less than 1 second and any equipment connected must not respond to such momentary changes of the relay This product should be fixed to...

Page 12: ...perating current 24 VDC version 0 030 A quiescent and 0 042 A alarm Battery backup 230 VAC version 1 x 6V 4 Ah Yuasa NP4 6 24 VDC version N A For information on routine battery changes refer to the Un...

Page 13: ...d fire alarm systems Part 25 Components using radio links European Union directives EMS declares that the radio equipment type Intelligent WZM is in compliance with Directive 2014 53 EU The full text...

Page 14: ...2021 EMS Ltd All rights reserved Page 14 of 14 TSD127 0001 99 Issue 1 05 05 2021 AJM www mysmartcell co uk...

Reviews: