3 / 3
p/n 483933 Rev. 3/12
LSI Industries Inc. 10000 Alliance Road Cincinnati, Ohio 45242 (513) 793-3200 Fax (513) 793-0147 www.lsi-industries.com
Installation Questions?
Call LSI Field Service Department at:
1-800-436-7800 Ext. 3300
Fax: 1-877-861-1368
Crossover® XCHM3 LED, cont'd.
ALL UNITS:
6. Position luminaire over all-thread. Feed supply wiring through center hole on back of luminaire. Use supplied
hardware to secure luminaire to pole and/or arm bracket. To ensure level luminaire, tighten upper nut first,
then lower nut, (tighten each to 25 ft-lbs.) making sure luminaire and/or arm is "square" to pole.
WARNING: Wiring to be performed by qualified electrician! Wire per National Electrical Code and local code.
IMPORTANT: Reference luminaire label for input voltage! Luminaire can be connected to 120-277VAC, 50/60
Hz or 347-480V, 60Hz only.
IMPORTANT WIRING INFORMATION - Risk of electrical shock!
* Make certain supply wiring is not "Hot" before wiring luminaire.
* Make certain supply voltage corresponds to luminaire voltage, as marked on luminaire label.
7. Close door. Be careful not to pinch any wiring between door and housing. Install pole cap. If ordered and
equipped, install photocell or photocell shorting cap.
8. The luminaire and pole assembly is now ready for installation to anchor bolts. When erecting pole, use belts,
slings or ropes - do NOT use chain or cable. Do not attach to luminaire or arm!
NOTE: Pole must be pointed in right direction. See Step 2 for proper light output direction for each
reflector type.
9. Set and level pole using nuts and washers provided.
SUPPLY WIRING
LINE NEU GRND
BLK WHT GRN
(LINE) (NEU) (GRND)
(2)
LUMINAIRE LEADS
OPTIONAL
TERMINAL BLOCK
WIRING DIAGRAM
SUITABLE WIRING
CONNECTORS
WHT BLK GRN
(2)
NEU LINE GRD.
CONNECT BOTH
HOUSING AND
DOOR GROUNDS!
CONNECT BOTH
HOUSING AND
DOOR GROUNDS!
SUPPLY WIRING