Smart temp SMT - 131 User Manual Download Page 10

 
Page 10 
 

Window Contact 

The window contact input (WC) is used to automatically disable the HVAC system if a window is 
left open. This is done to prevent energy waste by trying to heat or cool an open room. 
 
The SMT-131 window input can be set for a Normally Open (switch open when window is closed) 
or normally closed logic (switch closed when window is closed).  When the window is left open for 
longer than the pre-set time (0 to 300 seconds) the SMT-131 will automatically turn OFF. The text 
“OFF”  will  flash  in  the  LCD  to  indicate  that  the  remote  window  (or  door  switch)  is  holding  the 
SMT-131 in off mode. The wall controller will prohibit all changes. 
 
The SMT-131 will automatically restart once the window is closed. 
 
The  Installer  menu  option  28  “Window  Input  Logic”  and  option  29  “Window  Input  Delay” 

(page15)

 sets the window detection logic in the SMT-131. 

 

Door Switch 

The Door switch input (DS) is used by the SMT-131 for 2 functions.  

1)

 

To detect that the door has been opened and then closed to let somebody into or out 
of the room. 

2)

 

To detect if the door has been left open. 

 
The SMT door switch input can be set for a Normally Open (switch open when door is closed) or 
normally  closed  logic  (switch  closed  when  door  is  closed).    The  Installer  menu  30  “Door  Input 
Logic”  and  option  31“Door  Input  Delay” 

(page

Error!  Bookmark  not  defined.

)

  sets  the  door 

detection logic in the SMT-131. 
 

Entering or exiting the room. 

Once the door is opened and then closed the SMT-131 will begin its occupancy detection process 
using  the  PIR  input  described  below.  Based  on  the  outcome  of  this  process  the  SMT-131  will 
remain  on  and  permit  guest  interaction  with  the  SMT-131  (adjust  mode  and  set  point  for 
example), or switch to “un-occupied” mode where the SMT-131 will substitute the guest set point 
and mode for the installer pre-set values. 

 
Door Left Open 

When the door is left open for longer than the pre-set time (0 to 300 seconds) the SMT-131 will 
automatically turn OFF. The text “OFF” will flash in the display to indicate that the remote door 
(or window switch) is holding the SMT-131 in off mode. This is done to prevent energy waste by 
trying to heat or cool an open room. 
 
The SMT-131 will automatically restart once the door is closed. 
 

PIR input 

A PIR (passive infra-red) movement detector can be directly wired to the SMT-131 “PIR” input. As 
movement is detected by the PIR it will send multiple On/Off pulses to the SMT-131 every time it 
detects movement. The SMT-131 using this data along with door switch data will determine the 
occupancy  status  of  the  room  and  behave  accordingly.    Note,  the  PIR  must  be  separately 
powered, typically from a 12VDC supply. 
 

 

 

Summary of Contents for SMT - 131

Page 1: ...SMT 131 Manual Ver 2 1...

Page 2: ...ic and High fan limit Index Index 2 Introduction 3 Thermostat operation 3 Installation HVAC Control 4 DIP Switch Settings 5 Wiring HVAC Control 5 0 10v Outputs 7 Belimo 6 Way Valve 8 2 Pipe Mode 8 Anc...

Page 3: ...e thermostat to operate and has been designed to not require a user manual The diagram to the left shows all LCD elements and the 7 buttons Up Down Make Up Room Do Not Disturb On Off mode Fan Mode Deg...

Page 4: ...sfaction Please read and understand this instruction manual so that installation testing and commissioning process is undertaken in an effective and efficient manner Opening Wall Controller Open the S...

Page 5: ...4V Neutral R 24V Active This voltage is switched back through the relays Hi Indoor Fan High Speed NOT Used in Single fan speed mode Sw 1 OFF Med Indoor Fan Medium Speed NOT Used in Single fan speed mo...

Page 6: ...is damage is NOT covered by warranty Take care when wiring 24V near sensor inputs or the Modbus communications terminals Note When the SMT 131 calls heating or cooling the SMT 131 will drive both the...

Page 7: ...tput is used to control a heating valve A3 Fan This output is used to control a variable speed fan or a variable capacity AC system If the fan mode is set to Auto speed the 0 10V output will vary betw...

Page 8: ...is full heating and full cooling 1 C from set point The heating and cooling span can be adjusted independently to a maximum of full heating and full cooling 3 C from set point The output is linear No...

Page 9: ...system As shown in the picture the SMT 131 accepts door window and PIR contact inputs to automatically control temperature set points The HOT 243 wall controller mounted in the hallway outside of the...

Page 10: ...closed The Installer menu 30 Door Input Logic and option 31 Door Input Delay pageError Bookmark not defined sets the door detection logic in the SMT 131 Entering or exiting the room Once the door is o...

Page 11: ...ay have been some time since the door was closed Installer option PIR Input Delay page Error Bookmark not defined sets the PIR mode On or Off and the seek time value 1 to 15 minutes Manual Occupancy I...

Page 12: ...ipset that will theoretically permit the connection of up to 255 devices on a single Modbus node RF noises and other interferences will reduce the real world permitted connections to a maximum of 150...

Page 13: ...131 has an impressive list of options that can be installer selected These options tune the thermostat s performance as well as set energy conservation settings This menu is deliberately hidden and d...

Page 14: ...Fan purge 10 min 5 Heat only fan purge 1 min 6 Heat only fan purge 3 min 7 Heat only fan purge 5 min 8 Heat only fan purge 10 min 9 Cool only fan purge 1 min 10 Cool only fan purge 3 min 11 Cool only...

Page 15: ...nly 1 Always On high 2 Low when standby high when active Default 27 TT sensor SI Com 0 Remote Use this sensor in place of the fitted sensor 1 Average Use both remote and fitted sensor and control to t...

Page 16: ...s registers are shown as Base 1 PLC addressing format Depending on your modbus master addressing format you may need to subtract 1 from these values to convert to base 0 protocol addressing format Not...

Page 17: ...Point Deg C 0 5 C Steps Deg F 1 F Steps Value 10 e g 23 5 C 235 40010 Read Write Contact Reception Notification 0 Off 1 Show Contact Reception on LCD SMT 131 LCD will flash Contact Reception on LCD an...

Page 18: ...C to 3 C in 0 5 C Steps 1 F to 6 F in 1 F Steps Value 10 e g Heat Span of 1 C 10 40020 Read Write 0 10V Cool Span 0 5 C to 3 C in 0 5 C Steps 1 F to 6 F in 1 F Steps Value 10 e g Cool Span of 1 C 10...

Page 19: ...40029 Read Write Belimo Mode 0 Standard 0 10V Valve Logic 1 Belimo 6V Off 3 Way Valve Logic 40030 Read Write Modbus Address 1 to 255 40031 Read Write Baud Rate 1 4 8Kbs 2 9 6kbs 3 19 2Kbs 40032 Read...

Page 20: ...Minimum Voltage 0 10v Fan value x 10 40052 Read Write 0 10 Heat Interval 10 300 seconds in 10 second steps 60 seconds default 40053 Read Write 0 10 Heat Direction 0 10V is 100 open forward acting 1 0V...

Page 21: ...Range 5 C to 30 C 41 F to 86 F Memory Type Non Volatile Settings Do Not Require Battery Backup Communications Modbus RTU 4 8K 9 6K 19 2 K 1 Stop Bit 8 Data Bits 1 Start Bit No Parity Plastic ABS Poly...

Reviews: